background image

4

V. Principles of Operation

If ambient air cannot be utilized directly as a cooling medium, another cost-effective
method of cooling is a Water-to-Air system (below).  Water is used to remove heat from
the air circulated within the electronics enclosure.
Cooling water is circulated through a tube-and-fin coil.  As the heat-laden air circulates
through the coil, the heat is absorbed by the water and carried away, in a continuous
process.

Water-to-Air systems are easy to install and usually require minimum maintenance.
The water used must be reasonably clean and cold enough to ensure proper operation
of the cooling system under the most severe anticipated conditions.  In some cases, if
sufficiently cold water is available, below-ambient-temperature cooling can be
achieved.

VI. Specific Model Data

Mounting

Panel Mounted Heat Exchangers are equipped with two vertical mounting rails.
Using these rails, the units may be mounted to any available vertical surface on the
enclosure.

Refer to page 5 for location of all mounting holes and cutouts.

Make sure cutouts do not interfere with components inside your cabinet.

Proper alignment of air inlets and outlets is essential for optimum Heat Exchanger
performance.

All Kooltronic externally mounted Heat Exchangers are fully gasketed to ensure
proper sealing.  This seal is necessary to maintain the integrity of the closed-loop
system.

Use all existing mounting holes to insure stability and a tight seal.

Heated Air

Blower

Water

with

Heat Load

Cold

Water

Heat

Exchanger

Cabinet

Cooled Air

WATER-TO-AIR

A Water-to-Air Heat Exchanger works by transferring heat of internal
air to circulating water, resulting in chilled air which is recirculated
throughout the electronics or electrical cabinet.

Содержание KXHE240

Страница 1: ...G AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 041 04 3 19 CDR 20146 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...Kooltronic Heat Exchangers are designed to provide a cool environment for your electronic or electrical components There are models to fit virtually all sizes and shapes of electrical or electronic enclosures Our closed loop design also ensures that your components will not be exposed to hot dirty operating conditions This Manual provides you with the necessary general information for properly ins...

Страница 3: ...er until you read and thoroughly understand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate This nameplate provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate MODEL NO SERIAL NO...

Страница 4: ...ieved VI Specific Model Data Mounting Panel Mounted Heat Exchangers are equipped with two vertical mounting rails Using these rails the units may be mounted to any available vertical surface on the enclosure Refer to page 5 for location of all mounting holes and cutouts Make sure cutouts do not interfere with components inside your cabinet Proper alignment of air inlets and outlets is essential fo...

Страница 5: ...18 6 21 2 51 2 311 4 61 2 3 4 KXHE125 281 2 81 4 17 19 183 8 151 2 113 4 8 7 33 4 31 2 99 16 6 5 8 KXHE245 471 4 81 4 17 19 183 8 151 2 113 4 26 31 2 25 8 51 4 201 8 83 4 5 8 KXHE365 591 2 81 4 17 19 183 8 151 2 117 8 34 31 2 13 4 811 16 287 16 83 4 1 KXHE240 4 115 2 4 230 160 131 27 56 60 K2XHE240 4 230 1 9 230 160 131 27 56 60 KXHE360 4 115 2 4 230 160 131 55 90 80 K2XHE360 4 230 1 9 230 160 131...

Страница 6: ... through the heat exchanger element It is not possible to recommend specific filter cleaning intervals since the level and the nature of air borne particulate matter differs widely with each installation It is generally sufficient to remove and wash the reusable aluminum mesh air filter when the outer surface of these filters appear covered with a thin layer of dust or lint Filter recoating adhesi...

Страница 7: ...to the near retainer b press filter against the unit and c slide forward into far retainer CAUTION Do not operate the Heat Exchanger for extended periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element is not readily detected and will give the same reaction as clogged filter A clean filter...

Страница 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: