background image

6

VII. Maintenance

Kooltronic Air-Cooled Heat Exchangers are designed to require only routine cleaning
of air filters and the heat exchanger element to assure unimpeded airflow through the
heat exchanger element. It is not possible to recommend specific filter cleaning inter-
vals since the level and the nature of air borne particulate matter differs widely with
each installation. It is generally sufficient to remove and wash the reusable alu-
minum mesh air filter when the outer surface of these filters appear covered with a thin
layer of dust or lint.  Filter recoating adhesive is recommended. Appropriate dis-
posable filters are available from Kooltronic.
If filter service is neglected or delayed, the heat exchanger will not perform at its design
capacity. The first indication of excessively clogged air filter is usually a gradual
increase of temperature within the equipment cabinet.  Continued operation under
these conditions will cause damage, shorten blower motor life and void the warranty.

1

1/

2

5

3/

16 

TYP.

POWER
CORD

FILTER

M/TAB

18

K

17

1/

16

WARM AIR RETURN
FROM ENCLOSURE

WARM AMBIENT
AIR OUTLETS

COOL AIR OUTLET
TO ENCLOSURE

WARM AIR RETURN
FROM ENCLOSURE

FILTERED AMBIENT
AIR INLET

COOL AIR OUTLET
TO ENCLOSURE

A

18

9/

16

18

9/

16

4 TYP.

1

1/

4

UNIT
OUTLINE

(J)

.250 DIA.

HOLES

A

B

G TYP.

1

1/

2

15

TYP.

(H)

.312 DIA.

HOLES

E

F

M/TAB
OUTLINE

C

D TYP.

9

7/

8

12

13/

16

12

1/

8

3

3/

16

2

7/

8

9

3/

4

1

3/

4

5

9/

16

17

3/

4

11/

16

3/

8

Dimensions (inches) are for reference only and are subject to change.

Figure 1

Drawings and Dimensions

UNIT MUST BE 12” MINIMUM ABOVE
FLOOR FOR FILTER ACCESS

MOUNTING PLAN

UNIT

M/TAB & CUTOUTS

DIMENSIONS 

(inches)

Model

A

B

C

D

E

F

G

H

J

K

Series 38

37

3/

4

36

11/

16

12

3/

4

12

3/

4

18

1/

8

2

1/

2

4

11/

32

6

27

37

Series 47

47

45

15/

16

12

1/

4

11

1/

4

27

3/

8

2

1/

2

4

8

33

46

1/

4

Series 59

59

58

16

1/

4

15

1/

4

38

1/

2

3

3/

8

4

8

39

58

1/

4

Содержание KNHX38 Series

Страница 1: ...ING THIS HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 07 12 18 CDR 20111 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...c TrimLine Heat Exchangers are designed for indoor applications with ambient temperatures from 50 F to 131 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general information for pro...

Страница 3: ...er stand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate This nameplate provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate MODEL NO SERIAL NO MAX CABINET VOLTS FREQ PH AMPS TEM...

Страница 4: ...0 00 11 Condenser Blower Capacitor 0452 06 0452 06 0452 03 Condenser Blower Blower Motor 0261 08 0261 08 0261 149 Evaporator Blower Assembly 6015 00 129 6015 00 129 604559 00 36 Evaporator Blower Capacitor 0452 06 0452 06 0452 03 Evaporator Blower Blower Motor 0261 08 0261 08 0261 149 Filter 10871F 10871F 10871F Above parts are for 115V units For 230V consult factory Technical Data KNHX38 115 3 00...

Страница 5: ...tuds installed on the heat exchanger side panels into the inclined slots of the M TAB 6 Carefully mark all mounting holes from the flanges of the heat exchanger to the cabinet wall All holes in the heat exchanger flange must be used to maintain the NEMA 4 rating 7 Remove the heat exchanger from the M TAB and drill 218 dia mounting holes in the cabinet Do not attempt to drill mounting holes in the ...

Страница 6: ...d air filter is usually a gradual increase of temperature within the equipment cabinet Continued operation under these conditions will cause damage shorten blower motor life and void the warranty 11 2 53 16 TYP POWER CORD FILTER M TAB 18 K 171 16 WARM AIR RETURN FROM ENCLOSURE WARM AMBIENT AIR OUTLETS COOL AIR OUTLET TO ENCLOSURE WARM AIR RETURN FROM ENCLOSURE FILTERED AMBIENT AIR INLET COOL AIR O...

Страница 7: ...e tab slide the filter into the near retainer b press filter against the unit and c slide forward into far retainer CAUTION Do not operate the Heat Exchanger for extended periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element is not readily detected and will give the same reaction as clog...

Страница 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: