V. Principles of Operation

If ambient air cannot be utilized directly as a
cooling medium, another cost-effective
method of cooling is a Water-to-Air system
(Figure 1). Water is used to remove heat
from the air circulated within the electronics
enclosure.

Cooling water is circulated through a tube-
and-fin coil. As the heat-laden air circulates
through the coil, the heat is absorbed by the
water and carried away, in a continuous
process.

Water-to-Air systems are easy to install and
usually require minimum maintenance. The
water used must be reasonably clean and
cold enough to ensure proper operation of
the cooling system under the most severe
anticipated conditions. In some cases, if
sufficiently cold water is available, below-
ambient-temperature cooling can be
achieved.

The Heat Exchanger with options --
Automatic Water Flow Control is shown on
Figure 2.

Heated Air

Ca

b

inet

Cooled Air

Water With

Heat Load

Cold
Water

Heat
Exchanger

Blower

WATER-TO-AIR

A Water-to-Air Heat Exchanger works by transferring heat of internal
air to circulating water, resulting in chilled air which is recirculated
throughout the electronics or electrical cabinet.

Water Control

Thermostat

Water With

Heat Load

Cold
Water

Heat
Exchanger

Blower

Cooled
Air

Heated
Air

Solenoid
Valve

Water
Control 
Regulator

Figure 2

Figure 1

The Adjustable Water Control Thermostat opens and closes a water solenoid
valve based on the set point and differential settings. A temperature sensor is
located in the airstream of the cabinet. The Adjustable Water Control
Thermostat has a factory set point of 75

°

F.

VI. Specific Model Data

Mounting

The Kooltronic Water-To-Air Heat Exchangers have been engineered to be installed easily. These units utilize
double layer gaskets. The first gasket layer is placed on the outside perimeter of the front panel that is sealed
against the customer enclosure. The second layer is placed on the two cutouts in the front panel. The first gasket
layer will allow a small amount of water between the two layers. The second gasket layer totally protects an
enclosure from ambient air, rain or hose down water. This gasket arrangement assures the integrity of the closed
loop system and is necessary to maintain the NEMA 4 rating. 

Prior to mounting, refer to the mounting drawing showing dimensions and locations of mounting holes and cutouts.
Prior to cutting or drilling, make sure that cutouts and mounting holes do not interfere with components inside the
cabinet. To avoid damaging your air conditioner, please read the following information before installation:

Содержание KNHE60 Series

Страница 1: ...AT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents 900 046 26 7 20 CDR 20272 ...

Страница 2: ...ntroduction Kooltronic Heat Exchangers are designed to provide a cool environment for your electronic or electrical components There are models to fit virtually all sizes and shapes of electrical or electronic enclosures Our closed loop design also ensures that your components will not be exposed to hot dirty operating conditions This Manual provides you with the necessary general information for ...

Страница 3: ...hanger until you read and thoroughly understand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification Label Each Kooltronic Heat Exchanger includes an identification nameplate This nameplate provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate MODEL NO SERIAL NO MAX...

Страница 4: ...r With Heat Load Cold Water Heat Exchanger Blower Cooled Air Heated Air Solenoid Valve Water Control Regulator Figure 2 Figure 1 The Adjustable Water Control Thermostat opens and closes a water solenoid valve based on the set point and differential settings A temperature sensor is located in the airstream of the cabinet The Adjustable Water Control Thermostat has a factory set point of 75 F VI Spe...

Страница 5: ...e mounting drawing 6 Attach overflow drain hose supplied to the drain exit at the bottom of the unit This hose must not be elevated above the exit port Improper mounting will impede the flow of condensate and may cause internal malfunctions 7 Attach supply line to 1 2 O D copper tubing Inlet on bottom of unit 8 Attach discharge line to 1 2 O D copper tubing Outlet on bottom of unit WARM AIR RETURN...

Страница 6: ...encies Special materials or finishes Special motors line cords or connectors Temperature Alarm HEAT AND WATER ALARM WE TO BK WE TO RD EXCESS HEAT ALARM WATER LEVEL ALARM BLACK H WHITE N TO CUSTOMER ALARM SYSTEM TERM BLOCK HEAT AND WATER ALARM BK RD WE THERMOSTAT N C N C N O N O COM COM RELAY 1 2 3 4 5 6 7 8 N O BK LEVEL SWITCH CIRCUIT SHOWN WITH LINE POWER OFF NC NO WE RD BK TO CUSTOMER LOW AIRFLO...

Страница 7: ...e listing of Major Component Replacements earlier in this manual VIII Packing Procedure Keep Heat Exchanger in proper upright position Pack Heat Exchanger in an appropriate carton preferably original carton if possible with adequate internal protective packaging making sure carton is marked properly For local controlled transportation strap carton where possible to a secure part of truck to preven...

Страница 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: