background image

18

Unit not cooling. (Temperature

Failed Evaporator Blower.

Check Blower wire connections.

difference between return and

Check blower capacitor.

supply air is less than 10°F).

Replace Evaporator Blower.

Compressor and Condenser Blower
are running. Evaporator Blower does
not run.

Unit not cooling. (Temperature

Low Refrigerant charge.

Check discharge and suction pressure for

difference between return and

Refrigerant leak.

supply air is less than 10°F).

Failed Condenser Blower.

Check Blower wire connections.

Compressor and Evaporator Blower 

Check Blower Capacitor.

are running. Condenser Blower does

Replace Condenser Blower.

not run.

Failed Speed Controller.

Check Speed Controller Sensor.
Replace Speed Controller.

Unit not cooling. (Temperature

Condenser or Evaporator

Clean Coil.

difference between return and

Coil clogged.

supply air is less than 10°F).

Evaporator Blower, Condenser

Loss of Refrigerant.

Locate and repair leak.

Blower and Compressor are running.

Ice on Evaporator Coil.

Clean Evaporator Coil.
Check discharge and suction pressure for 
Refrigerant leak.
Check for any obstruction of Evaporator airflow.
Check and seal all openings.

Excessive condensate 

Eliminate the frequency of door openings.

draining and loss of A/C 
sensible cooling performance.

Unit overcooling.

Failed Thermostat.

Check Thermostat wire connections

.

Evaporator Blower, Condenser

Replace Thermostat.

Blower and Compressor are running.

Failed Relay.

Replace Relay.

Compressor cycling more than

Short circuiting of air

Provide baffle in the enclosure separating A/C

10 cycles per hour.

between A/C discharge 

Outlet and inlet.

and inlet openings.

Excess vibration.

Defective motor in Blower.

Replace motor.

Defective wheel in Blower.

Replace wheel.

Bad Compressor.

Replace Compressor.

.

Trouble-Shooting (con’t)

Problem

Cause

Solution

Compressor and Condenser

Return temperature is

Normal Operation.

Blower do not run when initially

between Thermostat set

energized after 15 minutes.

point and differential
(

75°F to 86°F).

Unit not cooling. (Temperature

Failed Thermostat

Check Thermostat and Relay wire connections.

difference between return and

or Relay.

Replace Thermostat or Relay.

supply air is less than 10°F).

Evaporator Blower is running. 

Low Line Voltage.

Check Nameplate Voltage against supply Voltage.

Compressor and Condenser Blower
do not run. Return temperature is

Failed Compressor.

Check Compressor wire connections.

above set point plus differential (90°F).

Check Compressor overload.
Check Compressor Capacitor.
Replace Compressor.

Содержание K2A6C9HL48LV

Страница 1: ...L BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 77 1 19 CDR 20131 HAZARDOUS LOCATION SERIES K_A6C9HL48LV U S Pat No 9 157 670 B2 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...ooting 17 18 XII Warranty 19 NOTE Wiring Schematics are available on the specific model page of the Kooltronic website I Introduction Kooltronic Hazardous Location Air Conditioners HL Series are designed to provide a cool dehumidified environment for your electronic components Our closed loop design also ensures that your components will not be exposed to hot dirty operating conditions This Manual...

Страница 3: ...inimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the correct power source Minimum circuit ampacity should be at least 125 of the amperage found on the nameplate for the corresponding voltage Do not exceed the maximum fuse size...

Страница 4: ...ASS I DIVISION 1 GROUPS A B C AND D HAZARDOUS LOCATIONS TYPE X PURGE AND CLASS I DIVISION 2 GROUPS A B C AND D TYPE Z PURGE ENCLOSURES WHEN INSTALLED ON AN APPROVED PRESSURIZED ENCLOSURE AND CONNECTED TO PURGE PRESSURIZATION CONTROL SYSTEM PER NFPA496 ALSO SUITABLE FOR CLASS I ZONE 1 GROUPS IIA IIB PLUS HYDROGEN AND IIC AIR LEAKAGE 0 25 I W G PRESSURE CFM 0 1 INTERNAL PRESSURIZED VOLUME CU FT 2 4 ...

Страница 5: ... of combustible materials or unless all devices within have been de energized WARNING HIGH TEMPERATURE INTERNAL PARTS This Air Conditioner must not be opened unless the area atmosphere is known to be below the ignitable concentration of combustible materials or unless all devices within have been de energized for at least thirty 30 minutes WARNING FOR CLASS I ENCLOSURE After the Air Conditioner ha...

Страница 6: ...surized customer enclosure must be connected to the Purge Pressurized Control System by gas air lines in parallel The Kooltronic HL Series Air Conditioner must be powered from the pressurized customer enclosure power supply and the customer enclosure must be controlled by the Purge Pressurized Control System All electrical and electronic components in the Kooltronic HL Series Air Conditioner are l...

Страница 7: ...consists of a heater a heat control thermostat and a heater limiter The heater control thermostat is a bimetal disk with a fixed set point of 60 F When the entering evaporator air temperature rises above 60 F the heater shuts off and when the evaporator air temperature falls below 40 F the heater will engage The heater limiter features a manual reset This unit is equipped with a Temperature Alarm ...

Страница 8: ...e the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plus down arrow keys for 3 seconds the C or F LED starts blinking 8 2 Select the required parameter Press the SET key to display its value 3 Use up or down arrow keys to change its value 4 Press SET to ...

Страница 9: ...ap code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation restart with door open alarm y odc Compress status when open door no nPS Number of activation of pressure switch 15 0 15 did Digital input alarm delay 5 min 0 255 i1F Digital input configuration EAL i1P...

Страница 10: ...scharge ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F 9 Reset the thermostat to the factory setting 80 F 10 Turn off the electrical power and disconnect the air conditioner from the power source NOTE Before shipment all Kooltronic Air Conditioners are subjected to a performance test CAUTION VIII Customer Enclosure Requirements 1 The inter...

Страница 11: ... to the enclosure The contact closure may be used with their control system having a timer function and output signal The output signal would energize a solenoid valve equipped with a fixed orifice or an adjustable needle valve within the enclosure This would provide additional pressurized air for a selected period of time typically two to three minutes The relief valve utilized on the purge press...

Страница 12: ...ar the bottom of the air conditioner 5 The customer must connect the Purge Pressurized System control line to the Swagelok fitting B400 1 OR 1 4 inch NPT The customer has a choice of two connection fittings on the unit One is for internal connection and the other is for external connection see illustration below The unused fitting must be sealed with the provided cap NOTE Some earlier models may o...

Страница 13: ... 88 225 6 1 11 28 2 1 2 68 17 3 4 70 119 4 68 17 3 36 9 1 52 13 3 6 67 169 3 6 00 152 4 94 23 9 6 00 152 4 6 00 152 4 5 62 143 0 79 20 1 6 38 161 9 6 00 152 4 4 67 119 0 MOUNTING PLAN Dimensions inches metric are for reference only and are subject to change WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 1 2 K_A6C9HL48LV ...

Страница 14: ... 1219 2 10 93 277 5 31 7 9 24 10 612 3 1 38 35 1 10 28 261 2 PRESSURE COMPENSATION TERMINAL BLOCK 65 16 4 97 24 5 32 49 825 3 PURGE PRESSURE FITTING 1 4 NPT 1 3 2 4 2 DRAIN K_A6C9HL48LV Dimensions inches metric are for reference only and are subject to change Drawings and Dimensions con t 14 FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air Out WARM AIR RETURN FROM ENCL...

Страница 15: ...nd Class I Zone 2 Groups IIA IIB plus hydrogen and IIC Hazardous Locations when used with an approved Type Z Purge System on the electrical enclosure Temperature Classification is T 4 275 F 135 C Maintains NEMA Type 12 3R 4 4X Ratings per UL 50 Cabinets and Boxes Closed Loop Cooling Compressor Short Cycling Protector Filter Interior and Exterior Purge Connections Internal Corrosion Protection Pain...

Страница 16: ...hed under warm running water with clean side up If the accumulated dirt is oily washing in a detergent bath is recommended followed by a warm water wash as above After filter removal the exposed condenser coil must be cleaned by pressurized air or pressurized cleaning solution Dirty liquid will be removed through the condenser coil drain pan B Blowers The design life of the blowers used in all Koo...

Страница 17: ...nt controller or enclosure see below Removing Air Conditioner from Pressurized Enclosure Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR CONDITIONERS in this manual under Section III PRODUCT HANDLING F Removing Air Conditioner from Pressurized Enclosure Before removing a Kooltronic HL Series Air Conditioner from a pressurized enclosure it must be...

Страница 18: ...condensate Eliminate the frequency of door openings draining and loss of A C sensible cooling performance Unit overcooling Failed Thermostat Check Thermostat wire connections Evaporator Blower Condenser Replace Thermostat Blower and Compressor are running Failed Relay Replace Relay Compressor cycling more than Short circuiting of air Provide baffle in the enclosure separating A C 10 cycles per hou...

Страница 19: ... received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Air Conditioners must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Отзывы: