VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will
verify the shipping integrity of the system. Please follow the steps below prior to instal-
lation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum,

allowing  the system to warm-up particularly in winter months.

2. Refer to the identification label for proper electrical voltage and current requirements.

Then connect the power cord to a properly grounded and fused electrical supply.
Leave the electrical power off.

3. Note the factory thermostat setting which is typically 75 to 80°F.

4. Adjust thermostat to its maximum setting.

5. If your unit is equipped with an on-off switch, move it to the on position.

6. Turn electrical power on.

7. Verify that the evaporator blower or fan is running.

8. Adjust the thermostat to its minimum setting. The compressor should start. On units

equipped with a short cycle protector, the compressor will have a delayed start of 6
minutes from the time power is applied to the unit.

9. Verify that the condenser blower or fan is running. Note, on units equipped with a low

ambient kit, the start of the condenser fan or blower will be delayed until the system
pressures rise.

10. Operate the air conditioner for approximately ten (10) minutes. During this period no

unusual noise or vibration should be evident. Both the evaporator and condenser fans
or blowers should be delivering air through their respective discharge ports. The cool
air should be discharged should be less than 70°F when the room temperature is
between 70 and 80°F.

11. On units equipped with heaters, adjust both the cooling and heating thermostats to

their maximum settings. Verify that the compressor and condenser fan or blower has
stopped. Verify elevated discharge air temperature from the evaporator air discharge.

12. If your unit is equipped with an on-off switch, leave it in the on position. Return the

cooling thermostat to its original setting. If unit is equipped with a heater, return the
heating thermostat to its original position.

13. Turn off the electrical power source, and disconnect the air conditioner from the power

source.

14. If any cover plug is removed to adjust the unit, make certain to put back in place to

maintain the integrity of the closed-loop airflow system.

NOTE: Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a 

performance test.

The Air Conditioner must be standing in its proper mounting position for a

minimum of five (5) minutes prior to testing. Failure to follow this procedure

will cause permanent damage to the compressor.

6

Содержание K2A3C8WP 5 Series

Страница 1: ...BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609...

Страница 2: ...ntroduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enc...

Страница 3: ...e in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operati...

Страница 4: ...ber MFG Order Number e Before operating be sure that the power source matches these requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the u...

Страница 5: ...by means of the vapor compression refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm ai...

Страница 6: ...delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and cond...

Страница 7: ...upplied to the drain exit on the bottom or lower side panel of the Air Conditioner The optional field installed Condensate Evaporator is mounted underneath the Air Conditioner and the drain hose is co...

Страница 8: ...STMENT D 312 DIA HOLES 7 TYP C B 19 A E 2 1 185 16 131 2 11 2 DIA POWER CORD HOLE 3 19 3 E A 7 TYP B 1 3 D 312 DIA HOLES 161 2 183 8 C L 19 COOL AIR OUTLET TO ENCLOSURE WARM AIR RETURN FROM ENCLOSURE...

Страница 9: ...5 230 60 6 8 6 3 G G G G G K2A4C5WP _ _ 5 5000 1 5 2 0 1 5 230 50 5 8 6 1 G G G G G KA4C6WP _ _ 6000 1 5 2 0 1 5 115 60 11 8 12 8 G G G G G KA4C6WP _ _ 56 6000 1 5 2 0 1 5 115 50 60 11 8 12 8 G G G G...

Страница 10: ...H KA4C_WP28 KA4C_WP28 8000 BTU H KA4C_WP36 KA4C_WP36 KA3C8WP36 Part Part Number Part Number Part Number Compressor 0665 101 0665 103 0665 42 Compressor Capacitor N A N A 0452 32 Condenser Coaxial Coil...

Страница 11: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet f...

Страница 12: ...valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refri...

Страница 13: ...ntrol Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Appli...

Страница 14: ...unted Cooled Mini NP33 Horizontal Accessories and Options HS P24 P47 NP36 Rack Top Panel MM NM P28 P52 NP47 Mounted Mounted Mounted SM NP17 P36 P59 NP59 H V HT WP Adapter Plate for Rack Mounting N A N...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: