9
If the air conditioner is mounted to the cabinet door you must be sure that the door hinges
will support the additional weight of the air conditioner. Also be certain that when the door
is opened fully, the cabinet does not become unbalanced. The actual weight of the unit can
be found in the Technical Data on page 12.
VII. Specific Model Data
Mounting
The Kooltronic Special Purpose Air Conditioners KNA4C9DP47L-1 have been engineered to be installed easily. Prior
to mounting, refer to page 10 and 11 for the mounting plan and the general arrangement drawings showing
dimensions and locations of mounting holes and cutouts. Prior to cutting or drilling, make sure that cutouts and
mounting holes do not interfere with components inside the cabinet. To avoid damaging your air conditioner, please
read the following information before installation:
1.
These externally mounted air conditioners have two gasket layers
to ensure a proper seal. This seal is necessary to maintain the
integrity of the closed-loop system and the enclosure NEMA 4 or
NEMA 4X Rating.
2.
Attach two hooks to the air conditioner using two #10 torx screws
for each hook.
3.
Hang the air conditioner on the enclosure upper cutout.
4.
Secure the air conditioner to the enclosure using (7)
1/
4
-20 x 1
1/
4
-
inch stainless steel bolts at the top and middle of the unit. Use (3)
stainless steel bolts
1/
4
-20 x 1
1/
4
-
inch and (3) stainless steel nuts
1/
4
-
20 on the bottom of the air conditioner.
5.
Attach plastic drain hose to the drain tubing on the bottom of the
air conditioner with a clamp.
HOOK
HOOK
CAUTION
Содержание Guardian KNA4C9DP47L-1
Страница 13: ...13 Wiring Diagrams ...