Principles of Operation (con’t)
RESETTING
If it becomes necessary to reset the unit, the factory settings are as follows:
7
PARAMETER
DESCRIPTION
VALUE UNIT
RANGE
MINIMUM
MAXIMUM
SEt
Set Point
75
°F
60
95
Hy
Differential
10
°F
1
45
dP4
Fourth probe display
0
--
--
--
dP3
Third probe display
0
--
--
--
dP2
Evaporator probe display
0
--
--
--
dP1
Room probe display
0
--
--
--
AFH
Differential for temperature alarm recovery
2
°F
1
45
ALL
Minimum temperature alarm
35
°F
-67
120
ALU
Maximum temperature alarm
120
°F
35
302
SHy
Differential for auxiliary relay
5
°F
1
45
SAA
Set point for auxiliary relay
115
°F
-67
302
ACH
Kind of action for auxiliary relay
CL
--
--
--
AC
Anti-short cycle delay
2
min
0
50
odS
Outputs delay at start up
0
min
0
255
P2P
Evaporator probe presence
n
--
--
--
ot
Thermostat probe calibration
0
°F
-21
21
US
Maximum set point
95
°F
75
302
LS
Minimum set point
60
°F
-67
75
Ptb
Map code
7
--
0
65535
rEL
Software release
0
--
--
--
rSE
Real set point
0
--
--
--
onF
on/off key enabling
ES
--
--
--
PbC
Kind of probe
ntc
--
--
--
Adr
Serial address
1
--
1
247
HES
Differential for energy saving
0
°F
-54
54
rrd
Regulation restart with door open alarm
y
--
--
--
odc
Compress status when open door
no
--
--
--
nPS
Number of activation of pressure switch
15
--
0
15
did
Digital input alarm delay
5
min
0
255
i1F
Digital input configuration
EAL
--
--
--
i1P
Digital input polarity
cL
--
--
--
dAO
Delay of temperature alarm at startup
00:00
h
--
--
ALd
Temperature alarm delay
0
min
0
255
ALc
Temperature alarms configuration
Ab
--
--
--
ArP
Probe selection for auxiliary alarm
P1
--
--
--
dLy
Display temperature alarm
00:00
min.
0
20
Lod
Probe displayed
P1
--
--
--
rES
Resolution
in
--
--
--
CF
Temperature measurement unit
F
--
--
--
CH
Kind of action: heating cooling
cL
--
--
--
COF
Compressor OFF time with faulty probe
4
min
0
255
COn
Compressor ON time with faulty probe
20
min
0
255
O4
Fourth probe calibration
0
°F
-21
21
P4P
Fourth probe presence
n
--
--
--
O3
Third probe calibration
0
°F
-21
21
P3P
Third probe presence
n
--
--
--
OE
Evaporator probe calibration
0
°F
-21
21