VIII. Maintenance

Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air
Conditioners are designed to require only the routine cleaning of air filters to assure
unimpeded air flow through the condenser heat exchanger. It is not possible to
recommend specific filter cleaning intervals since the level and the nature of airborne
particulate matter differs widely with each installation. It is generally sufficient to remove
and wash the reusable aluminum mesh air filters when the outer surfaces of these filters
appear covered with a thin layer of dust or lint. Filter recoating adhesive is recommended.
Appropriate disposable filters are available from Kooltronic.

If filter service is neglected or delayed, the air conditioner will not perform at its design
capacity. The first indication of excessively clogged air filters is usually a gradual
increase of temperature within the equipment cabinet. If operation is continued under
these conditions, the compressor will be shut off by the thermal overload device. The
compressor will restart when its external temperature drops below the protector threshold
setting and the compressor will continue to cycle on and off. Continued operation under
these conditions will cause damage, shorten compressor life and void the warranty.

A. Filter Removal and Service

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate
necessary cleaning.

CAUTION

1) Loosen the screw on the bottom of the filter holder.

2) Push the filter holder forward and move it down.

3) Remove the filter from the filter holder.

4) After removal, the filters should be flushed under warm running water with

the clean side up, driving contaminants out the dirty side of the filter. If the
accumulated dirt is oily, washing in a detergent bath is recommended, followed
by a warm water rinse as above.

5) The filters may be sprayed with 

Kooltronic A-16 Filter Recoating Adhesive

to

trap fine airborne contaminants, or they may simply be dried and reinstalled as
strainer type filters. 

Recoating is recommended for best results.

6) Reinstall the filter: Insert the filter inside the filter holder, push the filter holder forward,

move it up into place and replace the screw on the bottom of the filter holder.

Do not operate the Air Conditioner for extended periods of time with the

filter removed. The condenser coil may become clogged with dust or

lint from the air entering the face. A clogged condenser coil is not

readily detected and will give the same reaction as a clogged filter. A

clean filter is the best protection.

11

Содержание Advantage RP52 Series

Страница 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com ADVANTAGE RP52 SERIES 900 039 34...

Страница 2: ...ction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures...

Страница 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Страница 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Страница 5: ...ambient air by the condenser blower If latent heat exceeds 25 of the total cooling capacity excess condensate is released to the ambient through the drain tube The heat removed through the evaporator...

Страница 6: ...essor should start Units equipped with a Short Cycle Protector have a 3 minute delay from when the power is turned on until the compressor begins to operate 8 Verify that the condenser blower fan is r...

Страница 7: ...re inserted with heads on M TAB side Tighten nuts securely 5 Route the power cord through the top cut out in your cabinet Mount the unit to the M TAB by sliding the slots located on the front panel on...

Страница 8: ...1 356 0 18 28 464 2 15 96 405 3 52 56 1335 0 POWER CORD DRAIN 17 18 436 3 1 50 38 1 15 91 404 0 Drawings and Dimensions RP52 SERIES 8 Dimensions inches are for reference only and are subject to change...

Страница 9: ...Number Compressor 0665 50 Compressor Capacitor 0452 54 Condenser Blower Motor 0261 80 Condenser Blower Motor Capacitor 0452 06 Evaporator Blower Motor 0261 54 Evaporator Blower Motor Capacitor 0452 0...

Страница 10: ...K COOLING EFFECT DETECTOR CAP SUPPRESSOR TRANSFORMER WITH TEMP DISPLAY CRANKCASE HEATER HEATER HEATER OPTIONAL SHORT CYCLE PROTECTOR THERMAL CUT OUT T STAT SHORT CYCLE TIMER B C B R Y T STAT SET 75 F...

Страница 11: ...d off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable in...

Страница 12: ...ass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect re...

Страница 13: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Страница 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: