background image

II. Incoming Inspection

Kooltronic Air Conditioners are designed, built and packaged to withstand the shock and vibration normally
associated with shipment by common carriers. Occasionally improper handling during shipping causes damage.
Such handling could include unbanding of palletized shipments, failing to respect 

"This Side Up"

arrows, rough

handling, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be
done upon receipt of all shipments. Any carton tears, dents, scratches, loose articles or evidence of oil are signs
of damage and should be noted on the Freight Bill. Cartons should be opened promptly and the units inspected
for CONCEALED DAMAGE. Kooltronic Air Conditioners must be delivered in the proper mounting position to
assure that damage to the compressor has not occurred during shipping. Any Kooltronic Air Conditioner that is
delivered removed from the banded pallet, lying down or double stacked should be refused.

An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing
materials. Kooltronic cannot assume responsibility for Consignee's failure to file a timely freight claim.

III. Product Handling:

1) Do not attempt to operate your Kooltronic Air Conditioner until you read and thoroughly understand this

Manual. See section

VI PRE-INSTALLATION TESTING.

2) Before operating the Kooltronic Air Conditioner be certain that it is placed in its correct mounting position.

This Air Conditioner is designed to operate in a vertical position only. 

This placement must be done a

minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump
area. 

CAUTION

3) Before operating this unit, all electrical wiring must be checked to assure the proper connection to the correct

power source. Minimum circuit ampacity should be at least 125% of the amperage found on the nameplate
for the corresponding voltage. Do not exceed the maximum fuse size found on the nameplate.

4) We do not recommend that Air Conditioners be shipped to their final destination attached to an enclosure.

In the event that the Air Conditioner needs to be shipped attached to an enclosure it is strongly recommended
that proper support be provided for the Air Conditioner. Excessive vibration can occur if Air Conditioners
are not properly supported when shipped on enclosures, increasing the potential for internal damage and
voiding the warranty.

5)

PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR
CONDITIONERS:

Keep Air Conditioner in proper upright position indicated by arrow markers.

Pack Air Conditioner in an appropriate carton (preferably original carton if possible), with adequate
internal protective packaging, making sure carton is marked and is kept in correct upright position.

For local, controlled transportation, strap carton to a secure part of truck to prevent falling or
sliding, minimize vibration, etc.

For common carrier shipment, band unit(s) securely to a pallet. Unpalleted shipment risks
severe damage which voids the warranty.

3

Kooltronic Air Conditioners must be operated in their proper mounting position. If attempts are

made to operate a unit that is not in its designed mounting position, permanent compressor

damage will occur. This action will void the warranty. To avoid compressor damage do not tip the

unit more than 45° from its proper mounting position.

Содержание ADVANTAGE RP28 Series

Страница 1: ...CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 37 1 19 CDR 20131 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ...ge of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enclosures in capacities ranging from 1 000 to 30 000 BTU H Our closed loop design also ensures that your components will not be exposed to hot dirty operating conditions ...

Страница 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the correct power source Minimum circuit ampacity should be at least 125 of the amperage found on the nameplate for the corresponding voltage Do not exceed the maximum fuse size found on the namepl...

Страница 4: ...y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRANTY UNAUTHORIZED SERVICE OR MODIFICATION SERVICE AIR FILTER REGULARLY OUTDOOR USE COMPARTMENT ONLY NEMA EEMAC UL50 BY UNDERWRITERS LABORATORIE...

Страница 5: ...ed and returned Any enclosure moisture accumulated on the evaporator coil is collected and evaporated in the condensate evaporator tray and released to the ambient air by the condenser blower If latent heat exceeds 25 of the total cooling capacity excess condensate is released to the ambient through the drain tube The heat removed through the evaporator coil is transferred by the compressed refrig...

Страница 6: ...ayed start of six 6 minutes from the time power is applied to the unit 8 Verify that the condenser blower or fan is running Note the start of the condenser fan or blower will be delayed until the system pressures rise 9 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and condenser fans or blowers sh...

Страница 7: ...n nuts securely 5 Route the power cord through the top cut out in your cabinet Mount the unit to the M TAB by sliding the slots located on the front panel on the hooks of the M TAB 6 Tighten two screws on the bottom of the unit and seal the unit against the enclosure 7 Attach overflow drain hose supplied to the drain exit in bottom of the unit CAUTION If the Air Conditioner is mounted to the cabin...

Страница 8: ...3 4 Drawings and Dimensions RP28 SERIES 8 Dimensions inches mm are for reference only and are subject to change GA00356A Rev A FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air Out WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 1 2 3 4 ...

Страница 9: ...A4C_RP28R K2A4C_RP28R Parts Part Number Part Number Compressor 0665 116 0665 107 Condenser Blower Motor 0261 08 0261 54 Evaporator Blower Motor 0265 03 0265 06 Filter 7006F 7006F Standard Features Built in Condensate Evaporator CFC Free Refrigerant Crankcase Compressor Heater Digital Temperature Display Filter Head Pressure Control Switch Low Temperature Control Thermostat NEMA 12 3R Ratings Maint...

Страница 10: ...nd off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning CAUTION 1 Loosen the screw on the bottom of the filter holder 2 Push the filter holder forward and move it down 3 Remove the filter from the filter holder ...

Страница 11: ... bypass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is possible that shipping or other damage or microscopic leaks over a long period may result in the need for replenishment of refrigerant charge Whe...

Страница 12: ... applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged Evaporator Coil Clean Coil Condensate draining Enclosure not properly sealed Check and seal all openings continuously Excessive opening of Enclosure Eliminate the frequency of...

Страница 13: ...received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Air Conditioners must be returned in an upright position properly secured to a pallet Improper packaging may void war...