A high head pressure switch, which is standard on this unit, prevents the evaporator coil from freezing under low
ambient temperature. The crankcase compressor heater allows the unit to start with an ambient temperature of 0°F.
In applications having frequent voluntary or involuntary power interruptions, a compressor Short Cycle Protector is
recommended to allow adequate time for the internal pressures of the air conditioner to equalize before restarting. 

CAUTION

When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75°F to 115°F
enclosure temperatures, depending on ambient temperatures.

VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping
integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum, allowing the system to

warm-up. This is particularly important in winter months.

2. Refer to the nameplate for proper electrical voltage and current requirements. Then connect the power cord to

a properly grounded and fused electrical supply. Leave the electrical power off.

3. Elevate the unit approximately 3" above the floor to ensure proper condenser airflow. Do not block condenser

air inlet on bottom of unit.

4. Heat up sensor bulb in evaporator compartment to 90°F using a low temperature heat gun, or adjust the

thermostat to 55°F to simulate the need for cooling

5. Turn electrical power on.

6. Verify that the evaporator fan or blower is running.

7. The compressor should start. On units equipped with a Compressor Short Cycle Protector, the compressor will

have a delayed start of three (3) minutes from the time power is applied to the unit.

8. Verify that the condenser blower or fan is running. Note: The start of the condenser fan or blower will be delayed

until the system pressures rise.

9. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or vibration

should be evident. Both the evaporator and condenser fans or blowers should be delivering air through their
respective discharge ports. The cool air discharged should be less than 70°F when the room temperature
is between 70 and 80°F. 

10. Turn off the electrical power source, and disconnect the air conditioner from the power source.  

11. If the thermostat was lowered, adjust the thermostat back to 75°F. Failure to do this will result in coil freezing.

NOTE:

Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a performance test.

The temperature of the returning air to the air conditioner is displayed on the exterior

panel of the unit. This is considered the maximum temperature within the enclosure, and

not the temperature of the air supplied to the enclosure.

The Air Conditioner must be standing in its proper mounting position for a minimum of

five (5) minutes prior to testing. Failure to follow this procedure will cause permanent

damage to the compressor.

To access the thermostat, remove grille and upper panel. The thermostat is located in the upper corner

of the unit. all panels need to be re-installed to continue testing.

Содержание Advantage K2A3C5RP36R

Страница 1: ...RTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com ADVANTAGE RP36 SERIES 900 039 33 1 19 CDR 20131 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Страница 2: ... page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures in capacities ranging from 1 000 to 30 000 BTU H Our closed loop design also ensures that your components will not be exposed to hot dirty operating condition...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the correct power source Minimum circuit ampacity should be at least 125 of the amperage found on the nameplate for the corresponding voltage Do not exceed the maximum fuse size found on the name...

Страница 4: ...y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRANTY UNAUTHORIZED SERVICE OR MODIFICATION SERVICE AIR FILTER REGULARLY OUTDOOR USE COMPARTMENT ONLY NEMA EEMAC UL50 BY UNDERWRITERS LABORATORIE...

Страница 5: ... ambient air by the condenser blower If latent heat exceeds 25 of the total cooling capacity excess condensate is released to the ambient through the drain tube The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil Ambient air or water is then passed through the condenser coil where it absorbs the heat and is then discharged to the environm...

Страница 6: ...need for cooling 5 Turn electrical power on 6 Verify that the evaporator fan or blower is running 7 The compressor should start On units equipped with a Compressor Short Cycle Protector the compressor will have a delayed start of three 3 minutes from the time power is applied to the unit 8 Verify that the condenser blower or fan is running Note The start of the condenser fan or blower will be dela...

Страница 7: ...n nuts securely 5 Route the power cord through the top cut out in your cabinet Mount the unit to the M TAB by sliding the slots located on the front panel on the hooks of the M TAB 6 Tighten two screws on the bottom of the unit and seal the unit against the enclosure 7 Attach overflow drain hose supplied to the drain exit in bottom of the unit CAUTION If the Air Conditioner is mounted to the cabin...

Страница 8: ... 01 355 8 9 41 238 9 Drawings and Dimensions RP36 SERIES Dimensions inches are for reference only and are subject to change GA00375A Rev A FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air Out WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 1 2 3 4 ...

Страница 9: ...perate at 100V 50 Hz or 200V 50 Hz respectively No transformer is required Major Component Replacements KA4C_RP36R K2A4C_RP36R Part Part Number Part Number Compressor 0665 103 0665 106 Compressor Capacitor N A N A Condenser Blower Motor 0261 08 0261 54 Condenser Blower Motor Capacitor 0452 03 0452 03 Condenser Blower Assembly 200047 00 42 200047 00 43 Evaporator Blower Motor 0261 120 0261 121 Evap...

Страница 10: ...n and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning CAUTION 1 Loosen the screw on the bottom of the filter holder 2 Push the filter holder forward and move it down 3 Remove the filter from the filter hold...

Страница 11: ... bypass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is possible that shipping or other damage or microscopic leaks over a long period may result in the need for replenishment of refrigerant charge Whe...

Страница 12: ... applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged Evaporator Coil Clean Coil Condensate draining Enclosure not properly sealed Check and seal all openings continuously Excessive opening of Enclosure Eliminate the frequency of...

Страница 13: ...received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Air Conditioners must be returned in an upright position properly secured to a pallet Improper packaging may void war...