7.  Trouble check list 

 

- Only skilled personnel is allowed to execute these works! 

 1)

 

 

Malfunction 

If the control light for malfunction a/c (H218) is on, the reasons might be the followings: 

• 

short circuit of the digital outputs 

• 

no feedback from the compressor or from the circulated air gate 

• 

short circuit of sensors 

• 

cable failure of sensors 

If there is a malfunction, the control light is on until the fault is eliminated. With a certain computer 
program  the  faults  can  be  called  up  in  plain  text  and  deleted  when  the  fault  is  eliminated.  When 
there is a short circuit the short-circuit-proof outputs are checked 5 times and afterwards switched 
off and a malfunction is registered. When the malfunction is deleted out off the memory the output 
is  unblocked.  If  there  is  a  short  circuit  or  a  cable  failure  in  the  sensor,  a  malfunction  is  registered 
with  a  delay  of  approx.  30  seconds.  If  there  was  only  a  briefly  interruption  of  the  sensor,  the  fault 
message remains but the sensor controls furthermore using the actual sensor value. 

Trouble 

Cause 

Repair 

only by refrigeration expert

1)

 

a/c is not running 

thermostat is opened 

check inside temperature 

2)

 

reset thermostat 

2)

 

 

electric wiring disconnected 

check wiring at switch plate 

 

relay defective 

check relay and replace, if necessary 

 

defrosting thermostat cuts off 

check  evaporator  blower  and  replace,  if 
necessary 

 

too low outside temp. 
(possible icing of evaporator) 

switch on "ventilation" only 

2)

 

 

dirt on evaporator coil 

clean evaporator coil with compressed air 

 

compressor  does  not  com-
press 

check  pressure  at  suction  and  discharge 
side replace compressor, if necessary 

 

too  high  pressure  caused  by 
high outside temperature 

let unit run until pressure is stabilized

2)

 

 

leak  in  unit,  deficiency  or  re-
frigerant 

check unit for leaks 

recharge refrigerant, 

 

too high pressure 

check if axial fans are running 

check automatic fuse 

clean condenser coil with compressed air 

 

low pressure, drier clogged 

replace drier 

 

too  low  pressure,  screen  of 
expansion valve clogged 

clean screen; renew drier 

strong  noise  at  com-
pressor 

Defect  bearing  on  compres-
sor. 

replace  ball  bearing  or  complete  com-
pressor only 

 

slack V-belt 

check V-belt at compressor drive 

 

magnetic clutch 

check connections at magnetic clutch 

 

1)

 see handbook  „

KONVEKTA

 Service Stations“ 

2)

 operator is allowed to execute these works 

Содержание KL60CT/4

Страница 1: ...aftersales konvekta com Tel 49 6691 76 0 Internet www konvekta com Fax 49 6691 76 200 Operating Instruction for KONVEKTA Air Conditioner KL60CT 4 fully automatic version With digital air conditioning control system KS105 R134a 24Volt DC Compressor FKX4 KV4 FKX24 KV5 FKX40 KV6 ...

Страница 2: ... unit 8 4 1 Task of the air conditioning unit 8 4 2 Function of the air conditioning unit 8 4 2 1 Return Air Mixed Air Fresh Air Flap 8 4 2 2 Evaporator Blowers 8 4 2 3 Cooling Operation 9 4 2 4 Heating Process 9 5 Operator Controls 10 5 1 Operation panel function of the keys 10 6 Maintenance Servicing 11 6 1 Period of maintenance 11 6 2 Return air grid 11 6 3 Condenser coil 11 7 Trouble check lis...

Страница 3: ... repair and loss of time The national prescriptions for accident prevention and environment protection are to be added to this instruction The Operating instruction belong to the air conditioner Please keep one copy handy in the driver s cabin You will certainly understand that we will not recognize any warranty claims due to unproper han dling inadequate maintenance applications that do not corre...

Страница 4: ... that scope of supply depends on the order equipment of your product may differ in some parts of description In case your product is equipped with details not shown or described in the operating in struction your KONVEKTA Service Station will always be at disposal for informing you about correct operation In the course of further developments we reserve the right to technical modifications without...

Страница 5: ... compressor 2 If the vehicle is used for a longer time without using the cooling unit it is recommended to acti vate the compressor every two weeks Otherwise the shaft packing of the compressor could be damaged by vibrations of the motor Refrigerant R134a The chlorine free refrigerant R 134a is used for charging the air conditioner The traditional refriger ant R 12 is replaced by R 134a Air condit...

Страница 6: ...steröl SE55 2l Esteröl SE55 2l Magnetic clutch2 24V DC 24V DC 24V DC 1 2 2 Type FKX Compressor Type FKX40 465 555 650 FKX4 FKX24 465 650 Weight 1 35 kg 45 kg 39 kg Oil brand quantity Esteröl SE55 2l Esteröl SE55 2l Esteröl SE55 2l Magnetic clutch2 24V DC 24V DC 24V DC 1 Weight without Electro magnetic clutch witch clutch app 10kg 2 ø depending on vehicle type for articulated bus ...

Страница 7: ...ease of switch S362 are applicable If one of the 3 signals is interrupted control system starts to close all outlets SELF CONTROL If control system on 24VDC is connected self control is started in order to execute a trouble check of the whole system Short circuit of the digital outlets Re registration from compressor and return air flap Sensor data Internal system Setpoint room temperature If auto...

Страница 8: ...amages It s recommended to contact one of KONVEKTA s Service Stations 1 and the unit should first be taken into operation again after it has been checked through specialists 4 2 1 Return Air Mixed Air Fresh Air Flap In dependence to the outside temperature air flap is automatically changing to return mixed or fresh air Outside temperature 30 C up to approx 10 C Circulated Air 10 C up to approx 18 ...

Страница 9: ...e main water valve The digital outlet has a coast down time of 10 minutes maximum If heating and cooling performance is required outlet heating performance is automatically in operation Roof Heating The roof top unit is equipped with a water valve driven with a direct current motor Depending on status of the pole valve will be opened or close In order to avoid that valve is opened or closed immedi...

Страница 10: ...ment does not accelerate the cooling process but leads possibly to a damage on the operation panel and spoils the total functioning of your air conditioner 5 1 Operation panel function of the keys BBZW0014 BBZW0015 S362 H218 S363 S411 a c switch signal lamp switch Reheat Smog switch disturbance REHEAT Humidity Extraction While activating switch Reheat S363 compressor starts to work for 20 minutes ...

Страница 11: ...refully the KONVKETA safety pre scriptions TD00052A2 in order to avoid dangers and accidents 6 1 Period of maintenance At least once a year only by refrigerant expert 1 Check unit for leakages Retighten fixing screws of compressor and bracket at the engine Check electrical connections Check refrigerant Level at sight glass If air bubbles are formed consult service station Check hoses and electric ...

Страница 12: ...uble Cause Repair only by refrigeration expert1 a c is not running thermostat is opened check inside temperature 2 reset thermostat 2 electric wiring disconnected check wiring at switch plate relay defective check relay and replace if necessary defrosting thermostat cuts off check evaporator blower and replace if necessary too low outside temp possible icing of evaporator switch on ventilation onl...

Страница 13: ...ts free of charge is made subject to our verification of the defective parts later on If this inspection shows that the damages are due to improper handling we reserve ourselves the right to send you our invoice for the costs that have arisen Assumption for the validity of possible warranty claims is that the complete proof of all prescribed inspections and service works which have to be registere...

Отзывы: