1.3. Indicators

Classification

Indicator

Description

Meaning

AC Input

Lx

AC input

indicators

Steady on:Input voltage more than the threshold voltage

(90VAC)

Off:Input voltage less than the threshold voltage

(90VAC)

Downstream

Serial Port

RXD

RS485 data

receive

indicator

Steady on:RS485 line fault, please check if the positive

and negative poles of 485 line are reversed

Flashing:RS485 receiving data

Off:RS485 no receiving data

TXD

RS485 data

transmit

indicator

Flashing:RS485 transmitting data

Off:RS485 no transmitting data

Power

PWR

Power indicator

Steady on:Normal power supply

Off:No power or abnormal power supply, please check if

the voltage range is 9~27VDC

RUN

RUN

Running

indicator

Steady on:Device exception

Flashing:Flashes every 1 second when the device is ready

Off:Device exception

C2000-A2-SDX6000-CX1 User Manual

7 / 11

SinoCon Co., Ltd. 

www.sinoconsys.com

Содержание C2000-A2-SDX6000-CX1

Страница 1: ...Last updated 2019 12 13 C2000 A2 SDX6000 CX1 User Manual RS485 6AC AC 90 275V Remote I O Module AC Digital Input Module SinoCon Co Ltd ...

Страница 2: ...dware Description 1 1 Specifications 1 2 Apprearance 1 3 Indicators 1 4 Port Description 1 5 Product Dimensions 1 6 Installation Method 2 Package Contents 3 Warranty Policy C2000 A2 SDX6000 CX1 User Manual 2 11 SinoCon Co Ltd www sinoconsys com ...

Страница 3: ... liability stated by SinoCon in the terms and conditions of sale of its products and SinoCon makes no warranties regarding the sale or use of KonNaD products including the suitability for the specific use of the products and marketability and SinoCon doesn t guarantee that it won t infringe any patent copyright or other intellectual property rights etc Information in this document is subject to ch...

Страница 4: ...C2000 A2 SDX6000 CX1 User Manual 4 11 SinoCon Co Ltd www sinoconsys com ...

Страница 5: ...Serial Port Serial Standrad RS485 No of Ports 1 Connector Terminal block Serial Protocol Modbus RTU Power Power Connector Terminal block Input Voltage 9 27VDC Current 30mA 12VDC Power 0 3W Physical Characteristics Dimensions 75 105 30mm Installation Din rail or wall Environmental Limits Operating Temperature 40 85 Storage Temperature 60 125 Ambient Relative Humidity 5 95 RH non condensing C2000 A2...

Страница 6: ...1 2 Apprearance C2000 A2 SDX6000 CX1 User Manual 6 11 SinoCon Co Ltd www sinoconsys com ...

Страница 7: ...ive poles of 485 line are reversed Flashing RS485 receiving data Off RS485 no receiving data TXD RS485 data transmit indicator Flashing RS485 transmitting data Off RS485 no transmitting data Power PWR Power indicator Steady on Normal power supply Off No power or abnormal power supply please check if the voltage range is 9 27VDC RUN RUN Running indicator Steady on Device exception Flashing Flashes ...

Страница 8: ...re AC neutral wire Upstream Serial Port RS485 RS485 upstream RVSP 2 0 5 Power Input V V Power supply input positive power supply input negative RVV 2 1 0 PE Used for reliable grounding of the device surge protection RVV 2 0 5 C2000 A2 SDX6000 CX1 User Manual 8 11 SinoCon Co Ltd www sinoconsys com ...

Страница 9: ...1 5 Product Dimensions unit mm inch 1 6 Installation Method C2000 A2 SDX6000 CX1 User Manual 9 11 SinoCon Co Ltd www sinoconsys com ...

Страница 10: ...2 Package Contents No Contents 1 Device contain mounting kit 1 2 Terminal block 1 set 3 Installation guide card 1 C2000 A2 SDX6000 CX1 User Manual 10 11 SinoCon Co Ltd www sinoconsys com ...

Страница 11: ...y period or that have been improperly installed incorrectly input voltage improperly used accidental events or natural disasters etc are not covered by the warranty 3 Before accepting the warranty service the customer is required to prove the date of purchase of the product by presenting the warranty card or purchasing the invoice Otherwise the warranty cannot be guaranteed 4 For all warranty or r...

Отзывы: