Parameter detail setup
© Copyright Reserved KONICS Co., Ltd.
73
8.1.19
Burnout Action (Display setting for break)
In case Input Type(Input specification) is temperature sensor(thermocouple, RTD), set alarm
operation and alarm option for break input. (In case Input Type(Input specification) is
analog(voltage, current), this function does not operate.)
Set value
Description
OFF
When input break, after moving display value downward or upward according to
circuit structure
※
1
(max. or min. value in graph record state) it displays BURN.
Up Scale
When input break, after moving display value only upward (records max. value in
graph record state) it displays BURN.
Down Scale
When input break, after moving display value only downward (records min. value
in graph record state) it displays BURN.
Set range: OFF
↔
Up Scale
↔
Down Scale
Factory default: OFF
According to circuit structure, when thermocouple(Thermo Couple) temperature sensor,
RTD(RTD) temperature sensor’s A-B terminal or voltage input
±
60mV,
±
200mV input is break,
it displays Down Scale.
When RTD(RTD) temperature sensor’s B-B' terminal input is break, it displays Up Scale.
Содержание krn100
Страница 1: ... Copyright Reserved KONICS Co Ltd i USER MANUAL ...
Страница 2: ...ii Copyright Reserved KONICS Co Ltd ...
Страница 12: ...Table of Contents xii Copyright Reserved KONICS Co Ltd ...
Страница 26: ...2 Specification 26 Copyright Reserved KONICS Co Ltd ...
Страница 28: ...3 Dimensions 28 Copyright Reserved KONICS Co Ltd ...
Страница 32: ...4 Connection 32 Copyright Reserved KONICS Co Ltd ...
Страница 45: ...7 Operation Copyright Reserved KONICS Co Ltd 45 7 Operation ...
Страница 52: ...7 Operation 52 Copyright Reserved KONICS Co Ltd 7 3 2 Parameter ...
Страница 54: ...7 Operation 54 Copyright Reserved KONICS Co Ltd ...
Страница 144: ...9 DAQMaster 144 Copyright Reserved KONICS Co Ltd ...
Страница 150: ...10 Maintenance 150 Copyright Reserved KONICS Co Ltd ...
Страница 153: ...11 Troubleshooting Copyright Reserved KONICS Co Ltd 153 ...
Страница 154: ......