
394149/D
167
Basic cable requirements
It is very important that all systems cables are installed correctly. All cables must be
properly supported and protected, and all relevant precautions must be made to prevent
unwanted noise.
Topics
Radio frequency interference, page 168
Physical protection of cables, page 168
Grounding of system cables, page 169
Cable connections and terminations, page 169
Cable identification, page 170
Cable glands and termination procedures, page 170
Cable trays
All permanently installed cables associated with the system must be supported and
protected along their entire lengths using conduits and/or cable trays.
The only exception to this rule is over the final short distance (maximum. 0.5 meters) as
the cables run into the cabinets/units to which they are connected. These short service
loops are to allow the cabinets to move on their shock mounts, and to allow maintenance
and repair.
1
Wherever possible, cable trays must be straight, accessible and placed so as to
avoid possible contamination by condensation and dripping liquids (oil, etc.).
They must be installed away from sources of heat, and must be protected against
physical damage. Suitable shields must be provided where cables are installed
in the vicinity of heat sources.
2
Unless it is absolutely unavoidable, cables should not be installed across the vessel's
expansion joints. If the situation is unavoidable, a loop of cable having a length
proportional to the possible expansion of the joint must be provided. The minimum
internal radius of the loop must be at least twelve times the external diameter of
the cable.
3
Where a service requires duplicate supply lines, the cables must follow separate
paths through the vessel whenever possible.
4
Signal cables must not be installed in the same cable tray or conduit as high-power
cables.
5
Cables containing insulation materials with different maximum-rated conductor
temperatures should not be bunched together (that is, in a common clip, gland,
Содержание Simrad EK80
Страница 1: ...kongsberg com simrad Simrad EK80 INSTALLATION MANUAL ...
Страница 2: ......
Страница 12: ...10 394149 D Simrad EK80 ...
Страница 223: ...394149 D 221 6 Start the installation by selecting Next 7 Select Finish to close the wizard Setting to work ...
Страница 313: ...394149 D 311 Drawing file ...
Страница 314: ...312 394149 D Simrad EK80 Installation Manual ...
Страница 317: ...394149 D 315 Drawing file ...
Страница 318: ...316 394149 D Simrad EK80 Installation Manual ...
Страница 320: ...318 394149 D 201575 Transducer connector assembly and wiring Simrad EK80 Installation Manual ...
Страница 352: ... 2020 Kongsberg Maritime ISBN 978 82 8066 182 1 ...
Страница 353: ......
Страница 354: ...Installation Manual Simrad EK80 ...