background image

Graphic Operator Terminal
Installation Manual

Edition A, July 2013

AKI-CDA-MOD-07T 7” Touchscreen HMI

Keep all manuals as a product component during the life span of the product.
Pass all manuals to future users / owners of the product.

Содержание AKI-CDA-MOD-07T

Страница 1: ...or Terminal Installation Manual Edition A July 2013 AKI CDA MOD 07T 7 TouchscreenHMI Keep all manuals as a product component during the life span of the product Pass all manuals to future users owners of the product ...

Страница 2: ...hich improve the performance of the device may be made without prior notice Printed in the United States of America This document is the intellectual property of Kollmorgen All rights reserved No part of this work may be reproduced in any form by photocopying microfilm or any other method or stored processed copied or distributed by electronic means without the written permission of Kollmorgen ky ...

Страница 3: ...nections and Peripherals 11 4 Technical Data 5 Chemical Resistance 5 1 Metal Casing 14 5 2 Touch Screen and Overlay 15 5 2 1 Autoflex EBA 180L 15 5 2 2 Touch Screen Surface 15 5 2 3 Autoflex EBA 180L 16 6 Operator Panel Drawings 6 1 Connectors 17 6 2 Communication Ports 17 6 3 AKI CDA MOD 07T Outline 18 7 Additional Installation Tips 7 1 Grounding the Operator Panel 19 7 2 Ethernet Connection in t...

Страница 4: ... understand and use Configuration is carried out on a PC using the Kollmorgen Visualization Builder configuration tool The project can then be transferred and stored in the operator panel itself Various types of automation equipment such as PLCs servos or drives can be connected to the Advanced Kollmorgen Interfaces In this manual the term the controller refers to the connected equipment This manu...

Страница 5: ...topic The LCD display liquid contains a powerful irritant In case of skin contact wash immediately with plenty of water In case of eye contact hold the eye open flush with plenty of water and get medical attention The figures in this manual serves an illustrative purpose Because of the many variables associated with any particular installation the supplier cannot assume responsibility for actual u...

Страница 6: ...or follow the table with cable and torque specifications below Terminal Block No Wire Size AWG TQ Lb In X1 X100 Phoenix connectors AWG 30 12 5 7 X1 X100 Anytek connectors AWG 24 12 3 5 These devices are Class 2 supplied programmable controllers industrial PCs for the use in industrial control equipment and are intended to be front panel mounted Type 1 and 4x for indoor use only 2 3 DuringInstallat...

Страница 7: ...esult in explosion Only use batteries recommended by the supplier During the warranty period the battery needs to be replaced by an authorized Kollmorgen service center 2 6 Dismantling andScrapping The operator panel or parts thereof shall be recycled according to local regulations The following components contain substances that might be hazardous to health and the environment lithium battery ele...

Страница 8: ...e Requirements Maximum installation plate thickness 11 mm Space requirements in millimeters when installing the operator panel 50 mm 50 mm 100 mm 100 mm 100 mm 204 mm 143 mm Note The dimensions onthedrawing are not proportional ky Kollmorgen July 2013 8 ...

Страница 9: ...le surface during installation Dropping the panel or letting it fall may cause damage 2 Use the cut out dimensions that are included on the outline drawing found in section Operator Panel Drawings and in the Technical Data table to cut a correct opening in the cabinet 3 Secure the operator panel in position using all the fastening holes and the provided brackets and screws x 4 0 5 1 0 Nm ky Kollmo...

Страница 10: ...V DC A D Controller Power B Ethernet C Connect cable A Connect cable B using an M5 screw and a grounding conductor as short as possible with a cross section of minimum 2 5 mm2 Connect cable C Connect cable D The recommended cross section of the cable is 1 5 mm2 5 Carefully remove the laminated film over the operator panel display to avoid static electricity that could damage the panel Note Whencon...

Страница 11: ... 2 2 OtherConnectionsand Peripherals Cables peripheral equipment and accessories must be suitable for the application and its environment For further details or recommendations please refer to the supplier ky Kollmorgen July 2013 11 ...

Страница 12: ...or COM1 RS232 and COM2 RS422 RS485 9 pin D sub contact with RS232 RTS CTS chassis mounted female with standard locking screws 4 40UNC Serialport for COM3 RS232 and COM4 RS422 RS485 9 pin D sub contact with RS232 RTS CTS chassis mounted female with standard locking screws 4 40UNC Ethernet 1 10 Base T 100Base T shieldedRJ 45 USB 1 USB Host 2 0 max output current 200 mA Processor 400 MHz ARM9 Externa...

Страница 13: ...ing to IEC 60950 and IEC 61558 2 4 UL and cUL The power supply must conform with the requirements for class II power supplies Display TFT LCD with LED backlight 800 480pixels 64 k colors Activearea of display W H 152 4 91 4 mm Operating temperature 10 C 60 C Storage temperature 20 C 70 C Relative humidity 5 85 non condensed ky Kollmorgen July 2013 13 ...

Страница 14: ...ance to the following chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above chemicals is demanded it is recommended to first test the chemical in a hidden spot of the metal casing The powder paint shows little or no resistance to the following chemicals at room t...

Страница 15: ...d oil Tomato ketchup Castor oil Methanol Trichloroacetic acid 50 Caustic soda 40 1 Nitric acid 10 White Spirit Cutting oil Paraffin oil Windex 1 Cyclohexanol Persil powder in solution 1 Wisk Diacetone alcohol Petroleum spirit 1 1 Extremely faint glossing of the texture was noted Autoflex EBA 180L withstands DIN 42 115 Part 2 exposure of up to 1 hour duration to glacial acetic acid without visible ...

Страница 16: ... be ordered from Kollmorgen Solvent Resistance Autoflex EBA 180L withstands exposure to the same chemicals as Autotex F157 or F207 according to section Autoflex EBA 180L Outdoor Use In common with all polyester based films Autoflex EBA 180L is not suitable for use in conditions of long term exposure to direct sunlight ky Kollmorgen July 2013 16 ...

Страница 17: ...00 Base T shielded RJ 45 4 COM 3 4 Communication Ports 6 2 Communication Ports Serial port 9 pin female Serial port 9 pin female Pin COM1 COM2 COM3 COM4 1 RS422 Tx RS485 Tx Rx RS422 Tx RS485 Tx Rx 2 RS232 RxD RS232 RxD 3 RS232 TxD RS232 TxD 4 RS422 Rx RS422 Rx 5 GND GND GND GND 6 RS422 Tx RS485 Tx Rx RS422 Tx RS485 Tx Rx 7 RS232 RTS RS422 RTS 8 RS232 CTS RS422 RTS 9 RS422 Rx RS422 Rx ky Kollmorgen...

Страница 18: ... PANEL DRAWINGS 6 3 AKI CDA MOD 07TOutline COM3 RS232 COM4 RS422 RS485 COM1 RS232 COM2 RS422 RS485 Ethernet 24 V DC Expansion port USB host SD memory card slot 126 143 9 9 7 43 max 11 mm 187 9 9 204 ky Kollmorgen July 2013 18 ...

Страница 19: ...is and the closest grounding point on the door see 3 in drawing above 3 Connect a strong but short grounding braid between the door and the device cabinet see 4 in drawing above 4 Twist the cables onto the 24 V DC feed see 5 in drawing above Minimum cross section of the cable is 2 5 mm2 2 turns around the ferrite core provide 4 times the suppression of 1 turn 3 turns around the ferrite core provid...

Страница 20: ... Ethernet unit has its shield directly grounded or grounded via a capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at bothends is inappropriate Hum or grounding loops can occur Unshielded cabling may even result in fewer communication errors A good solution may be to use a shielded Ethernet cable but to connect the shield at one end only One option is to break t...

Страница 21: ...ernative is to connect the other end of the shield to the ground via a 0 1 µF 250 V plastic capacitor Both ends are then connected to the ground in terms of HF but only connected to the ground at one end in terms of LF thus avoiding the 50 60 Hz grounding loops Metal cabinet Metal cabinet Terminal or connector Terminal or connector EMC cable gland Plastic cable gland Shielded cable Short distance ...

Страница 22: ...nsitive to heat The lifespan of an electrolytic capacitor is cut in half with an 8 10 C increase in temperature A 15 20 C temperature increase results in a quarter of the lifespan etc Rittal has a good program for estimating the anticipated average temperature in the cabinet as well as a large program for controlling the temperature in the device cabinet An enamel coated steel cabinet has a radian...

Страница 23: ... example SELV according to EN 60950 protection against electric shock and UL 950 Example Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller controller Check that the clearances and creepage distances between 24V DC and 230 V AC fulfillEN 60950 or UL 950 If not input a separate 24 V unit into the operator ...

Страница 24: ...for example a USB memory stick keyboard or similar device is plugged in If a number of units are connected that have a 0 V and a ground connection and these are connected to various grounding points there is a substantial risk of problems Grounding currents go through communication cables the rear plate of the controller and internally in the operator panel and can cause errors Use external units ...

Страница 25: ... shield must be grounded at one end The other end is usually grounded but with longer distances or when there is a difference in the ground potential the shield should be connected to the ground via 0 1 µF 250 V plastic capacitor to prevent ground current in the braided shield A number of manufacturers recommend that the shield be grounded at each node Various manufacturers have different systems ...

Страница 26: ...marketplace advantage For assistance with your application needs visit www kollmorgen com or contact us at North America Europe Asia KOLLMORGEN KOLLMORGEN Europe GmbH KOLLMORGEN 203A West Rock Road Pempelfurtstraße 1 Rm 2205 Scitech Tower China Radford VA 24141 USA 40880 Ratingen Germany 22 Jianguomen Wai Street Web www kollmorgen com Web www kollmorgen com Web www kollmorgen com Mail support koll...

Отзывы: