background image

AKI-CDA-MOD-04T | OPERATOR PANEL DRAWINGS

6

OPERATOR PANEL DRAWINGS

6.1

Connectors

1

2

3

4

COM 3/4

LAN

COM 1/2

Pos.

Connector

Description

1

Power supply

+24 V DC (18-32 V DC)

2

COM 1/2

Communication Ports

3

LAN

1 × 10/100 Base-T (shielded RJ45)

4

COM 3/4

Communication Ports

6.2

Communication Ports

Serial port, 9-pin female

Serial port, 9-pin female

Pin

COM1

COM2

COM3

COM4

1

-

RS422 Tx+

RS485 Tx+/Rx+

-

RS422 Tx+

RS485 Tx+/Rx+

2

RS232 RxD

-

RS232 RxD

-

3

RS232 TxD

-

RS232 TxD

-

4

-

RS422 Rx+

-

RS422 Rx+

5

GND

GND

GND

GND

6

-

RS422 Tx-

RS485 Tx-/Rx-

-

RS422 Tx-

RS485 Tx-/Rx-

7

RS232 RTS

-

-

RS422 RTS+

8

RS232 CTS

-

-

RS422 RTS-

9

-

RS422 Rx-

-

RS422 Rx-

ky

Kollmorgen | October 2014

17

Содержание AKI-CDA-MOD-04T

Страница 1: ...Terminal Installation Manual Edition B October 2014 AKI CDA MOD 04T 4 3 TouchscreenHMI Keep all manuals as a product component during the life span of the product Pass all manuals to future users owne...

Страница 2: ...TICE Technical changes which improve the performance of the device may be made withoutprior notice Printed in the United States of America This document is the intellectual property of Kollmorgen All...

Страница 3: ...eripherals 11 4 Technical Data 5 Chemical Resistance 5 1 Metal Casing 14 5 2 Touch Screen and Overlay 15 5 2 1 Autoflex EBA 180L 15 5 2 2 Touch Screen Surface 15 5 2 3 TouchKeyboard and Screen Protect...

Страница 4: ...derstand and use Configuration is carried out on a PC using the Kollmorgen Visualization Builder configuration tool The project can then be transferred and stored in the operator panel itself Various...

Страница 5: ...ontact hold the eye open flush with plenty of water and get medical attention The figures in this manual serves an illustrative purpose Because of the many variables associated with any particular ins...

Страница 6: ...ed Do not recharge disassemble or dispose of in fire LA BATTERIE PEUT EXPLOSER EN CAS DE MAUVAISE MANIPULATION NE LA RECHARGEZ PAS NE LA D MONTEZ PAS ET NE LA JETEZ PAS DANS LE FEU For use on a flat s...

Страница 7: ...n 2 5 Service andMaintenance Only qualified personnel should carry out repairs The agreed warranty applies Before carrying out any cleaning or maintenance operations disconnect the equipment from the...

Страница 8: ...uirements Maximum installation plate thickness 11 mm Space requirements in millimeters when installing the operator panel 50 mm 100 mm 100 mm 100 mm 104 mm 50 mm 145 mm 43 mm Note The dimensions onthe...

Страница 9: ...able surface during installation Dropping the HMI panel or letting it fallmay cause damage 2 To cut a correct opening for the HMI panel use the cut out dimensions in the outline drawing For more infor...

Страница 10: ...Controller Power B Ethernet C Connect cable A Connect cable B using an M5 screw and a grounding conductor as short as possible that is sized correctly according to local electrical codes Connect cable...

Страница 11: ...2 OtherConnectionsand Peripherals Cables peripheral equipment and accessories must be suitable for the application and its environment For further details or recommendations please refer to the suppli...

Страница 12: ...r COM1 RS232 and COM2 RS422 RS485 9 pin D sub contact with RS232 RTS CTS chassis mounted female with standard locking screws 4 40UNC Serialport for COM3 RS232 and COM4 RS422 RS485 9 pin D sub contact...

Страница 13: ...d cUL The power supply must conform with the requirements for class II power supplies Display TFT LCD with LED backlight 480 272pixels 64 k colors Activearea of display W H 95 0 53 9 mm Operating temp...

Страница 14: ...to the following chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Sodium hypochlorite 10 Turpentine Note If exposure to any o...

Страница 15: ...tchup Caustic soda 40 1 Methanol Trichloroacetic acid 50 Cutting oil Nitric acid 10 White Spirit Cyclohexanol Paraffin oil Windex 1 Diacetone alcohol Persil powder in solution 1 Wisk Diesel Petroleum...

Страница 16: ...lex EBA 180L Outdoor Use In common with all polyester based films Autoflex EBA 180L is not suitable for use in conditions of long term exposure to direct sunlight Note The layer structure of the touch...

Страница 17: ...Base T shielded RJ45 4 COM 3 4 Communication Ports 6 2 Communication Ports Serial port 9 pin female Serial port 9 pin female Pin COM1 COM2 COM3 COM4 1 RS422 Tx RS485 Tx Rx RS422 Tx RS485 Tx Rx 2 RS23...

Страница 18: ...NEL DRAWINGS 6 3 AKI CDA MOD 04TOutline COM1 RS232 COM2 RS422 RS485 24 V DC COM3 RS 232 COM4 RS422 RS485 Ethernet USB host SD memory card slot Expansion port 87 104 43 9 9 9 9 128 9 7 max 11 mm 145 ky...

Страница 19: ...ccording to local electrical codes between the operator panel s chassis and the closest grounding point on the door see 3 in drawing above 3 Connect a strong but short grounding braid between the door...

Страница 20: ...thernet unit has its shield directly grounded or grounded via a capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at bothends is inappropriate Hum or grounding loops...

Страница 21: ...end of the shield to the ground via a 0 1 F 250 V plastic capacitor Both ends are then connected to the ground in terms of HF but only connected to the ground at one end in terms of LF thus avoiding t...

Страница 22: ...itive to heat The lifespan of an electrolytic capacitor is cut in half with an 8 10 C increase in temperature A 15 20 C temperature increase results in a quarter of the lifespan etc Rittal has a good...

Страница 23: ...example SELV according to EN 60950 protection against electric shock and UL 950 Note Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V A...

Страница 24: ...r example a USB memory stick keyboard or similar device is plugged in If a number of units are connected that have a 0 V and a ground connection and these are connected to various grounding points the...

Страница 25: ...hield must be grounded at one end The other end is usually grounded but with longer distances or when there is a difference in the ground potential the shield should be connected to the ground via 0 1...

Страница 26: ...Tap anywhere on screen or touch calibrate will start in 10 seconds 5 Press finger on screen again to enter the service menu The Service Menu displays Note Additional information about the Service Menu...

Страница 27: ...y right clicking on the System option in the Project Explorer and select Add HMI Device to display a list of HMI panels that Kollmorgen has available Double click on the project to launch KVB and auto...

Страница 28: ...arketplace advantage For assistance with your application needs visit www kollmorgen com or contact us at North America Europe Asia KOLLMORGEN KOLLMORGEN Europe GmbH KOLLMORGEN 203A West Rock Road Pem...

Отзывы: