AKD PDMM User Guide | 28.51 DRV.OPMODE
General Information
Default
Value
N/A
Data Type
String
See Also
Returns how long the drive has been running since first activated. (pg
296)
Start Version M_01-00-00-000
Description
This parameter returns the length of time that the drive has been running for the current session
(since the last power up).
28.51 DRV.OPMODE
General Information
Type
NV Parameter
Description
Sets the drive operation mode (current, velocity, or posi-
tion).
Units
N/A
Range
0 to 2
Default
Value
0
Data Type
Integer
See Also
Start Version M_01-00-00-000
Fieldbus
Index/Subindex Object Start Version
EtherCAT COE and CAN-
open
/0
M_01-00-00-000
Description
DRV.OPMODE specifies the operation mode of the drive. You must also use
DRV.CMDSOURCE to set the source of the command to the drive.
The operation mode values can be set as follows:
Mode
Description
0
Current (torque) operation
mode
1
Velocity operation mode
2
Position operation mode
DRV.OPMODE can be changed while the drive is enabled or disabled. If you are using the ter-
minal to change the operation mode, then it is recommended that you disable the drive before
changing the operation mode. If you change the operation mode from the terminal while the
drive is enabled, the system may experience a step change in demand.
Example
Set the source of the command to a TCP/IP channel and the desired operation mode to veloc-
ity:
-->DRV.CMDSOURCE 0
-->DRV.OPMODE 1
294
Kollmorgen™ | December 2012
Содержание AKD PDMM series
Страница 25: ...This page intentionally left blank 25 Kollmorgen December 2012...
Страница 32: ...This page intentionally left blank 32 Kollmorgen December 2012...
Страница 52: ...This page intentionally left blank 52 Kollmorgen December 2012...
Страница 101: ...AKD PDMM User Guide 12 3 6 2 Biquad Calculations 101 Kollmorgen December 2012...
Страница 133: ...This page intentionally left blank 133 Kollmorgen December 2012...
Страница 158: ...AKD PDMM User Guide 17 Connection Diagrams Kollmorgen December 2012 158...
Страница 246: ...AKD PDMM User Guide 26 6 DIN1 INV to DIN7 INV Digital Inputs and Outputs 246 Kollmorgen December 2012...
Страница 340: ...AKD PDMM User Guide 33 11 FBUS TYPE 2 EtherCAT 3 CANopen 4 EthernetIP 5 Profinet 340 Kollmorgen December 2012...
Страница 470: ...AKD PDMM User Guide 48 27 VL THRESH 1 Velocity Loop 470 Kollmorgen December 2012...
Страница 511: ...This page intentionally left blank 511 Kollmorgen December 2012...
Страница 513: ...This page intentionally left blank 513 Kollmorgen December 2012...