Troubleshooting

Problem

Possible Causes

Dust is emitted from 
either the indoor or 
outdoor unit  

The unit may accumulate dust during extended periods of non-use, which 

will be emitted when the unit is turned on. This can be mitigated by covering 

the unit during long periods of inactivity.  

The unit emits a 
bad odor  

The unit may absorb odors from the environment (such as furniture, cooking, 

cigarettes, etc.) which will be emitted during operations. 
The unit’s filters have become moldy and should be cleaned.

The fan of the 

outdoor unit 

does not operate 

During operation, the fan speed is controlled to optimize product operation.

Troubleshooting Tips

When troubles occur, please check the following points before contacting a repair company. 

Problem

Possible Causes

Solution

The unit 
is not 
working 

Power failure

Wait for the power to be restored

The power switch is off

Turn on the power

The fuse is burned out

Replace the fuse

Remote control batteries are dead

Replace the remote control batteries

The unit’s 3-minute protection has 

been activated 

Wait three minutes after restarting the unit 

Poor cooling 
performance 

Temperature setting may be higher 

than the ambient room temperature  Lower the temperature setting
The heat exchanger on the indoor 

or outdoor unit is dirty 

Clean the affected heat exchanger

The air filter is dirty

Remove the filter and clean it according 

to instructions

The air inlet or outlet of either unit 

is blocked

Turn the unit off, remove the obstruction 

and turn it back on 

Doors and windows are open

Make sure that all doors and windows are 

closed while operating the unit 

Excessive heat is generated by 

sunlight

Close windows and curtains during 

periods of high heat or bright sunshine 

Low refrigerant due to leak or 

long-term use

Check for leaks, re-seal if necessary and 

top off refrigerant 

The unit 
starts and 
stops 
frequently 

There’s too much or too little 

refrigerant in the system  

Check for leaks and recharge the system 

with refrigerant  

There is air, incompressible gas or 

foreign material in the refrigeration 

system.  

Evacuate and recharge the system with 

refrigerant

System circuit is blocked

Determine which circuit is blocked and replace 

the malfunctioning piece of equipment 

The compressor is broken

Replace the compressor

The voltage is too high or too low

Install a manostat to regulate the voltage

Poor heating 
performance 

The outdoor temperature is lower 

than 7°C (44.5°F) 

Check for leaks and recharge the system 

with refrigerant 

Cold air is entering through doors 

and windows

Make sure that all doors and windows are 

closed during use  

Low refrigerant due to leak or 

long-term use

Check for leaks, re-seal if necessary and 

top off refrigerant 

Содержание KLM-SS40-4F1M

Страница 1: ...al carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Unit models KLM SS40 4F1M KLM SS70 4F3M 8VHU 0DQXDO Ceiling Cassette Air Conditioner www kolinphil com ph ...

Страница 2: ...Indoor Unit Parts and Major Functions 06 Manual Operations 08 Table of Contents Owner s Manual SAFETY FIRST Safety Precautions 04 1 2 3 ...

Страница 3: ...ing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants For more details please refer to the Information on servicing on INSTALLATION MANUAL This is only required for the unit adopts R32 R290 Refrigerant ...

Страница 4: ...not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater The appliance shall be stored so as to prevent mechanical damage from occurring Be aware that the refrigerants may no...

Страница 5: ...es thoroughly ventilate the room to avoid oxygen deficiency DO NOT climb onto or place objects on top of the outdoor unit DO NOT operate the air conditioner when using fumigant insecticides The chemicals may become layered with the unit and endanger those who are hypersensitive to chemicals DO NOT let children play with the air conditioner DO NOT operate the air conditioner in a wet room e g bathr...

Страница 6: ... C 5 F 76 F 0 C 50 C 32 F 122 F 18 C 54 C For special tropical models 0 C 60 C For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER When outside temperature is below 0 C 32 F we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance 7 C 24 C Inverter Split Type COOL Mode HE...

Страница 7: ...et and outlet of the unit This will reduce the efficiency of the unit Set a timer and use the built in SLEEP ECONOMY mode if applicable If you don t plan to use the unit for a long time remove the batteries from the remote control Clean the air filter every two weeks A dirty filter can reduce cooling or heating efficiency Adjust louvers properly and avoid direct airflow Louver Angle Memory Functio...

Страница 8: ...ver Infrared receiver Fig 3 1 Fig 3 2 MANUAL button This button selects the mode in the following order AUTO FORCED COOL OFF FORCED COOL mode In FORCED COOL mode the Operation light flashes The system will then turn to AUTO after it has cooled with a high wind speed for 30 minutes The remote control will be disabled during this operation OFF mode When the panel is turned OFF the unit turns off and...

Страница 9: ...r conditioning system and disconnect the power supply before cleaning or maintenance DO NOT use chemicals or chemically treated cloths to clean the unit DO NOT use benzene paint thinner polishing powder or other solvents to clean the unit They can cause the plastic surface to crack or deform DO NOT wash the unit under running water Doing so causes an electrical hazard DO NOT use water hotter than ...

Страница 10: ...ight will flash Preparation For Periods Of Non Use Maintenance after Extended Non Use 1 Remove any obstacles blocking the vents of both the indoor and outdoor units 2 Clean the air filter and the front grille of the indoor unit Reinstall the clean dry air filter in its original position 3 Turn on the main power switch at least 12 hours prior to operating the unit Storing the Unit While Not In Use ...

Страница 11: ...nit changes its setting to prevent frost from forming on the unit Once the temperature increases the unit will start operating again The set temperature has been reached at which point the unit turns off the compressor The unit will resume operating when the temperature fluctuates again The indoor unit emits white mist In humid regions a large temperature difference between the room s air and the ...

Страница 12: ... indoor or outdoor unit is dirty Clean the affected heat exchanger The air filter is dirty Remove the filter and clean it according to instructions The air inlet or outlet of either unit is blocked Turn the unit off remove the obstruction and turn it back on Doors and windows are open Make sure that all doors and windows are closed while operating the unit Excessive heat is generated by sunlight C...

Страница 13: ...protection 1 On F0 11 Outdoor temperature sensor error 2 On F 1 12 Outdoor condenser pipe sensor error 3 On F2 13 Discharge air temperature sensor error 4 On F3 14 Outdoor EEPROM Electrically Erasable Programmable Read Only Memory error 5 On F4 15 Outdoor fan speed DC fan motor only malfunction 6 On F5 16 17 Auto lifting panel communication error 8 On F7 18 Auto lifting panel malfunction 9 On F8 1...

Страница 14: ...ash Quick flash E6 7 EEPROM malfunction Quick flash Quick flash E7 8 Water level alarm malfunction E8 9 DC motor speed out of control Quick flash 10 Outdoor unit low pressure malfunction Quick flash Quick flash 11 Auto lifting panel communication error Quick flash F0 12 Auto lifting panel malfunction Quick flash F 1 13 Auto lifting panel is open On F2 14 Refrigerant leak detection system malfuncti...

Страница 15: ...aste When disposing of this appliance you have the following options Dispose of the appliance at designated municipal electronic waste collection facility When buying a new appliance the retailer will take back the old appliance free of charge The manufacturer will also take back the old appliance free of charge Sell the appliance to certified scrap metal dealers NOTE Disposing of this appliance i...

Страница 16: ...16122700000121 KPII20190405 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details ...

Страница 17: ......

Отзывы: