Roof Extractor HiFEK EC 18-36  

Instructions for Transport, Storage, 

Installation, Operation and 

Maintenance

 23.1.2015 

 

 

 

 

 

 

Connection marks of motor are as follows:  

L1, L2, L3, N:   Network access, phase sequency free,  (check the voltage in rating plate) 

PE:  

Protective earth 

11 and 14:   Running indication (n > 200 rpm)  

E1:  

Analog guideline value for rotation speed (0...10 V or PWM) 

D1:  

Digital input, enable device 

GND:  

Voltage reference  

10 V:  

DC output, max. 10 mA 

24 V:  

DC output, max. 70 mA 

 

Ru = Brown 

Si = Blue 

KeVi = Yellow/Green 

Va = White 

Mu = Black 

Ke = Yellow 

Vi = Green 

Pu = Red 

 

The motor needs a rotation speed set point for running. It can be formed

 

of the 10V

 

output

 

of the motor. In 

cold surroundings the heating of electronics is activated when the inside temperature is -

19˚C. That is why it 

is very important that the motor supply is never switched off. The motor can be stopped by means of control 

or by disconnecting the enable device. To prevent the impeller and motor from freeze-up, it is advisable to 

let the motor always run at least at the minimum speed (1.0V control). 

If the motor rotates freely e.g. in air flow, it may generate a voltage of more than 50V to connectors. 

Rotation of impeller has to be prevented and dead state has to be checked always before service works.  

 

Electornics of motor includes big condencers which may be dangerously live even after switching off the 

voltages. 

Wait at least three minutes after the disconnection of voltage before you start service or repair 

works

 

Mains voltage must absolutely be the same as given in the rating plate. Motors have integrated overload 

protection. Maximum value of fuse for all models is 10A. 

Maximum leakage current of the unit is 3.5 mA in mains conforming to the standard DIN EN 60990.  

Commissioning and operation 

Make sure that the roof extractor has been installed according to the instructions, and that there are no 

foreign objects loose inside.  

Also check that the electrical connection has been made according to the instructions enclosed in the 

delivery.  

Make sure that the fastening screws are tight enough in the stack and there is a raising rubber in every corner. 

Start the extractor and make sure the impeller rotates in the direction indicated by the arrow marked on the 

mounting plate. 

Make sure that the base plate is tightly fixed on the mounting surface of the mounting stack. 

 

Содержание HiFEK 18

Страница 1: ......

Страница 2: ...ow the given instructions especially the safety instructions See the separate instructions for electricity too Packing Roof Extractor HiFEK 18 36 is packed in plastic for transport storage and relocat...

Страница 3: ...belts and hooks must not be fastened inside the roof extractor Be careful not to cause damage to the components when handling the unit Lift and move the roof extractor in upright position Weights are...

Страница 4: ...k of tilting Note specially when hauling narrow and high parts the roof extractor is hauled in transport position the carrying capacity of haulage levels is sufficient the roof extractor is lifted wit...

Страница 5: ...or by the outlet grating or electric cables 2 Check before mounting that the mounting surface of the mounting stack is straight Mount the roof extractor to the stack or existing duct according to the...

Страница 6: ...ete duct Hexagon screw M8x55 8 8 FeZn DIN931 Washer 8 4 DIN 9021 FeZn Rubber cone plug D25 10 Raisin rubber s 10 Seal 15x30 Coach screw M8x80 FeZn DIN571 Washer 8 4 DIN 9021 FeZn Rubber cone plug D25...

Страница 7: ...o the instruction Roof extractors HiFEK 18 36 are equipped with 3 phase motors Further information on the connection and electrical features is found in the separate manual The standard model always i...

Страница 8: ...eely e g in air flow it may generate a voltage of more than 50V to connectors Rotation of impeller has to be prevented and dead state has to be checked always before service works Electornics of motor...

Страница 9: ...the hook is firmly in the lug Have the extractor serviced at the beginning and at the end of the heating season in autumn and in spring The extractor can be cleaned by the plant s own service personn...

Страница 10: ...tening screws in front of fan and six hinge screws behind the fan can then be lifted off Weight of roof extractors HiFEK 18 32kg HiFEK 24 59kg HiFEK 36 69kg Measuring of air flow Calculation of air fl...

Страница 11: ...are open that all air terminal devices have been installed that the dampers are open that the pressure loss of the ductwork is not bigger than estimated 3 The extractor does not start Check that the f...

Отзывы: