Section 2 Installation
Section 2 Installation
2.1 Introduction
Kohler
r
transfer switches are shipped factory-wired,
factory-tested, and ready for installation.
Have the
equipment installed only by trained and qualified
personnel, and verify that the installation complies with
applicable codes and standards. Protect the switch
against damage before and during installation.
2.2 Receipt of Unit
2.2.1
Inspection
At the time of delivery, inspect the packaging and the
transfer switch for signs of shipping damage. Unpack
the transfer switch as soon as possible and inspect the
exterior and interior for shipping damage. If damage
and/or rough handling is evident, immediately file a
damage claim with the transportation company.
2.2.2
Storage
Store the transfer switch in its protective packing until
final installation. Protect the transfer switch at all times
from moisture, construction grit, and metal chips. Avoid
storage in cold or damp areas where moisture could
condense on the unit. See Figure 2-1 for acceptable
storage temperatures.
Item
Specification
Storage
Temperature
--40
°
C to 85
°
C (--40
°
F to 185
°
F)
Operating
Temperature
--20
°
C to 70
°
C (--4
°
F to 158
°
F)
Humidity
5% to 95% noncondensing
Altitude
0 to 3050 m (10000 ft.) without derating
Figure 2-1
Environmental Specifications
2.2.3
Unpacking
Allow the equipment to warm to room temperature for at
least
24 hours
before
unpacking
to
prevent
condensation on the electrical apparatus. Use care
when unpacking to avoid damaging transfer switch
components. Use a vacuum cleaner or a dry cloth to
remove dirt and packing material that may have
accumulated in the transfer switch or any of its
components.
Note:
Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris
to lodge in the components and damage the
switch.
2.2.4
Lifting
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Use adequate lifting capacity.
Never leave the transfer switch
standing upright unless it is securely
bolted in place or stabilized.
WARNING
See Figure 2-2 or the dimensional drawing for the
weight of the transfer switch. Use a spreader bar to lift
the transfer switch.
Attach the bar only to the
enclosure’s mounting holes or lifting brackets; do not lift
the unit any other way. Close and latch the enclosure
door before moving the unit.
Amps
Description
Weight, kg (lb.)
[
100
Single phase
7
(14)
With load center
8.2
(18)
Three phase
14
(30)
Service Entrance
10
(22)
200
Single phase
7
(15)
Three phase
14
(30)
Service Entrance
12
(26)
400
Single phase
36
(80)
3-Pole/208--240 Volts
41
(90)
3-Pole/480 Volts
59
(130)
4-Pole
59
(130)
Service Entrance
46
(100)
Figure 2-2
Approximate Weights
Содержание RXT
Страница 10: ...TP 6807 12 11 10 Service Assistance Notes...
Страница 24: ...TP 6807 12 11 24 Section 4 Service Disconnect SE Model Notes...
Страница 28: ...TP 6807 12 11 28 Section 5 Scheduled Maintenance Notes...
Страница 36: ...TP 6807 12 11 36 Section 5 Diagrams and Drawings Figure 6 7 Enclosure Dimensions 400 Amp Single Phase ADV 8193...
Страница 42: ...TP 6807 12 11 42 Section 5 Diagrams and Drawings Figure 6 13 Wiring Diagram 100 400 Amp Single Phase GM80663...
Страница 43: ...TP 6807 12 11 43 Section 5 Diagrams and Drawings Figure 6 14 Schematic Diagram 100 400 Amp Single Phase GM80664...
Страница 54: ...TP 6807 12 11 54 Section 5 Diagrams and Drawings Notes...
Страница 57: ...TP 6807 12 11 57 Notes...
Страница 58: ...TP 6807 12 11 58 Notes...
Страница 59: ......