6
TS_602_01 PW1000/LT User Manual 20/3/19
1500/2200VA Model only (Fig D)
9. Using an insulated screwdriver, remove the two screws from the battery holding plate.
10. Loosen and disconnect the cable from the battery negative terminal followed by the red battery positive terminal.
11. Loosen and remove the link connecting the two batteries together (shown in green in the diagram)
12. Carefully withdraw the batteries from the case, taking care not to short circuit the battery terminals.
13. Fit the replacement batteries using the above instructions in reverse order. (Note that it is normal to see a small spark
when connecting the new battery.)
14. Refit the front panel and top cover, and secure in place using the four screws located at the base of the UPS.
5.2
Battery disposal
Batteries contain dangerous substances that can harm the environment if they are disposed of carelessly. ALWAYS
dispose unwanted batteries in accordance with regulations set by local environmental waste disposal organisations.
6
Troubleshooting
If the UPS fails to operate correctly, carry out the following simple checks before you seek trained assistance.
1. Check that the utility mains supply is available and turned ON.
2. Check that the UPS input mains power cable is connected securely.
3. Check that the utility mains supply is within the UPS specified operating range.
4. If the above checks are passed, and the UPS is still not operating, check the mains supply plug-top fuse and the input
fuse (2) on the back of the UPS and replace if found to be ruptured.
Seek trained assistance if the replacement fuse fails immediately the UPS is switched back ON.
5. If all of the above are satisfactory, disconnect the load from the UPS power outlet(s) and check if the unit operates off-
load. If so, then the cause of the problem is likely to be load related.
6. Check that the battery is not discharged or defective.
Symptom
Possible cause
Solution
No LEDs displayed on front panel
Battery voltage is low
Charge the UPS for at least 6 hours
Battery is defective
Replace battery with one of the same capacity
The UPS is not turned ON
Press the power switch again (3 seconds.)
Alarm beeps continuously when the
utility mains supply is normal
The UPS is overloaded
Reduce the connected load until it is within the UPS
specified load capacity
UPS does not provide the expected
back-up time
The UPS is overloaded
Reduce the connected load until it is within the UPS
specified load capacity
Battery voltage is low
Charge the UPS for at least 6 hours
Battery is defective
Replace battery with one of same capacity
Utility mains supply is normal but the
input LED is flashing
Mains power cable is loose.
Reconnect the mains power cable correctly