TS_616_08 PW8000DPA ST (S2) User Manual 21/4/22
49
4: Installation
4.3.2 Removing the alternative wooden crate packaging
1. Remove the wooden crate sides and top by removing the
securing screws from the bottom and sides of each panel
2. Carefully remove the accessories box that is shipped on top of
the main UPS cabinet.
3. Remove any cardboard or polystyrene fillets that are taped to the
outside of the plastic wrapping.
4. Remove the plastic wrapping by pulling it upwards over the top
of the cabinet.
Note: The edges of the cabinet are not protected, so if you have
to cut the wrapping take care not to scratch or damage the
cabinet paintwork.
5. Remove the four screws securing the pallet to the cabinet legs,
as indicated in Figure 4.4.
6. Using a forklift or pallet jack, raise the cabinet clear of the
ground.
a) Remove the pallet.
b) Fit the four adjustable levelling feet, found in the accessories
package, to the bottom of the cabinet legs.
7. Open the cabinet door, remove any further internal packaging
where applicable and inspect for internal damage. Report any
damage to the shipper immediately
8. If no damage is found, move the cabinet to its final location and
adjust the levelling feet as necessary.
9. Fit the painted front and back kick plates, found in the
accessories package, as required.
4.3.3 Batteries
Unless they are to be stored for a long period
, the batteries should remain in their packaging until
they are required by the Kohler Uninterruptible Power Ltd. commissioning engineer.
Battery life depends very much on temperature and should ideally be stored and operated at a temperature of 20°C.
CAUTION:
The UPS batteries must ALWAYS be installed by the commissioning engineer.
WARNING:
If the UPS is delivered without batteries, Kohler Uninterruptible Power Ltd. will not accept
responsibility for any damage or malfunctioning caused to the UPS by the incorrect storage, installation or
connection of batteries carried out by third parties.
Figure 4.5 Wooden crate packaging