3: Installation Planning
18
TS_610_01 PowerWAVE 6000 S3 (60-120kVA) User Manual 21/10/19
3.2.2 Installation clearances
Figure 3.1 illustrates the clearances required when installing a single or multi-module PW6000 (S3) UPS system. The top
illustrations show a single-module installation and a four-module parallel system installed as an equipment suite including
an adjacent CBAT 150T battery cabinet.
The lower illustration shows a four-module parallel system installed with a ‘remote’ battery enclosure.
Figure 3.1 Installation clearances
Top clearance (ventilation)
The UPS is force-cooled by conditioned air which enters the cabinet through the ventilation grills in the cabinet door and
then extracted by roof-mounted fans.
• A minimum of 400 mm must be provided above the UPS cabinet to allow an adequate extracted air flow.
• Consideration should also be given to ensure that the ventilation grills on the cabinet doors and top of the cabinet
are not likely to be obstructed.
Front clearance (A),(B)
The CBAT 150T battery cabinet requires a minimum of 1200 mm front clearance (A) to allow access its battery trays
• When installing a UPS ‘suite’ with the UPS cabinets aligned with the front of the CBAT 150T this front clearance (A)
also applies to the UPS cabinets.
• If the battery is installed in a remote enclosure the UPS cabinet front clearance can be reduced to 1000 mm (B).
Note: These are the specified ‘minimum’ clearances. Where possible, these clearances should be ideally increased to
allow safe passage in front of the UPS with the doors open.
Rear clearance (C),(D)
No rear clearance is necessary for cabinet ventilation purposes, and rear access is not required to install, connect or
operate the UPS. Therefore, the cabinet can be installed directly against a wall or partition where appropriate (C). Where
Key Point:
The CBAT 150T battery cabinet is recommended by Kohler Uninterruptible Power Ltd for use with
the PW6000 (S3) system. If an alternative battery cabinet is used then the dimensions shown in Figure 3.1 must
be adapted to suit the recommendations of the particular battery cabinet manufacture.
CBAT
150T
Battery
Cabinet
UPS
Cabinet
UPS
Cabinet
UPS
Cabinet
UPS
Cabinet
UPS
Cabinet
CBAT
150T
Battery
Cabinet
CBAT
150T
Battery
Cabinet
UPS Cab (WxDxH) = 615 x 480 x 1978
Batt Cab (WxDxH) = 630 x 985 x 1975
UPS
Cabinet
UPS
Cabinet
UPS
Cabinet
UPS
Cabinet
Bespoke Battery Enclosure
A
D
B
A
C
C
E
F
E
E
Содержание PowerWAVE 6000
Страница 1: ......
Страница 2: ...TS_610_01 PowerWAVE 6000 S3 60 120kVA User Manual 21 10 19 ...
Страница 4: ...TS_610_01 PowerWAVE 6000 S3 60 120kVA User Manual 21 10 19 ...