![Kohler PA-320741 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/kohler/pa-320741/pa-320741_operation-and-installation-instructions-manual_1987945011.webp)
9
TT-855 12/93
Installation
Mount Charger
1. Move generator master switch to OFF position.
Disconnect battery cables, negative lead first.
Open circuit breaker of AC power source to be
applied.
2. Turn automatic transfer switch selector to OFF
position.
3. Open automatic transfer switch enclosure.
4. Install four captive nuts (298811) in the transfer
switch inner panel and install battery charger. See
Figure 8.
5. The battery charger is factory set to maintain the
proper output for the battery voltage for which it is
rated. No customer adjustments are required.
Output Connections
NOTE
For DC connections use stranded copper wire, 600 Volt,
105
_
C vinyl plastic insulation UL style 1015, CSA type
TEW.
1. Due to the variety of generator installations,
battery cables are not provided. To make battery
connections, cut red (+) 10-gauge stranded wire
to proper length and strip insulation from both
ends. To one end of wire attach a post-type
connector. Route other end of battery cable and
connect to output positive (+) terminal on charger
DC terminal block. See Figure 8. Tighten terminal
block lock screw to secure battery cable. Repeat
procedure with black (–) 10-gauge stranded wire;
connect black wire to output negative (–) terminal
on DC terminal block and secure with lock screw.
2. Connect red charger lead(s) to battery positive (+)
terminal and black charger lead(s) to battery
negative (–) terminal.
Grounding Instructions—This battery charger should
be connected to a grounded, metal, permanent wiring
system. An equipment-grounding conductor could also
be run with circuit conductors and connected to
equipment-grounding terminal on battery charger.
Connections to battery charger should comply with all
local codes and ordinances.
Input Connections
1. Connect the correct voltage, 50/60 Hz, AC power
source as indicated by nameplate or transfer
switch wiring diagram.
2. Turn AC power on. Power On lamp will light and
ammeter will show charging current.