![Kohler M340+ Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/kohler/m340/m340_service-and-parts-manual_1989901049.webp)
4-22 Controller Troubleshooting
TP-5672 11/95
Yes
No
No
Does an entry appear in Index 20
that says OPTIONS LOCK? NO ?
Troubleshooting complete.
Replace logic board.
Interrupt controller power supply by
disconnecting the inline disconnect plug P1.
Wait at least one minute. Reconnect P1.
Does YES appear only after Index 11 listed
options with jumpers on JP1?
Options are not locked.
Lock the options to change:
Answer YES and ENTER to
OPTIONS LOCK? NO in Index 20, then
press RESET MENU then ENTER to
store the setpoints before repeating
powerdown/powerup sequence.
Yes
Yes
Yes
No
No
Options are locked. Does
OFF DELAYS not have a
jumper and displays YES ?
Check Index 20. Is the switch type
M GERIN MC ?
The OFF DELAYS are required
and cannot be changed to NO.
Figure 4-17. Troubleshooting— YES appears in Index 11 when a jumper for that option is not installed
Yes
Yes
No
Yes
Does an entry appear in Index 20
that says OPTIONS LOCK? NO ?
Options are not locked.
Lock the options to change:
Answer YES and ENTER to
OPTIONS LOCK? NO in Index 20,
then press RESET MENU then ENTER
to store the setpoints before repeating
powerdown/powerup sequence.
Troubleshooting complete.
Interrupt controller power supply by
disconnecting the inline disconnect plug P1.
Wait at least one minute. Reconnect P1.
Does YES appear only after Index 11 listed
options with jumpers on JP1?
Remove the jumpers of the options that
appears as NO in Index 11 and test for
continuity. Is any jumper open?
Replace logic board.
Replace open jumper.
No
Yes
Options are locked. Does OFF DELAYS
have a jumper and displays NO ?
Yes
Check Index 20. Is the switch type
ZENITH STD ?
TD OFF not available
on switches without
an Off position
No
Yes
Does INPHASE MONITOR
have a jumper and displays NO ?
Check Index 20. Is the switch type
ZENITH STD ?
IN-PHASE MONITOR not
available on switches
with an Off position
No
No
Yes
No
No
Figure 4-18. Troubleshooting— NO appears in Index 11 when a jumper for that option is installed