3 Handling, operation
3.1 Start-up procedure
3.1.1 Filling the operating fluids
Fill the following operating fluids before the initial commissioning:
–
Diesel engine oil
For suitable lubricating oil for the Diesel engine, see the chapter “Lubricants and
operating fluids”.
–
Coolant
For coolant composition, see the chapter “Lubricants and operating fluids”.
–
Diesel fuel
Diesel fuels must comply with the approved fuel specifications, see the chapter
“Lubricants and operating fluids”.
After filling the operating fluids, perform the following work:
u
Vent fuel system. Please refer to the generator sets' operating manual.
3.1.2 Starting the engine
Prerequisites:
q
The oil level is OK
q
Engine is filled with coolant
q
Charge air is connected
q
Exhaust system is connected
q
Electrical power supply is ready
q
Fuel supply is connected
WARNING
Unexpected movement of the equipment.
Can cause serious injuries or the death of persons.
u
There may be no persons in the safety zones of the diesel engine.
u
Bring all of the protective devices into their protective position (housing is
closed), if equipped.
u
Secure external parts against unexpected movements. Remove all persons
from the danger zones.
Information
Engine damage due to inadequate lubrication.
u
The oil pressure has to build up immediately after the diesel engine is started
(oil-pressure warning lamp goes out).
KD36V16 33521029701_1_1 en 2018-08-01
© 2018 by Kohler Co. All rights reserved.
33