40 Section 4 Communication and Accessory Connections
Alarm Silence Mode
In Alarm Silence Mode, the horn is disabled. Alarm
Silenced appears on the display and the system alert
LED lights.
The Alarm Silenced condition can be assigned to a
programmable output. See the controller operation
manual for instructions to assign outputs.
Instructions to Silence the Alarm in Normal and
Chicago Alarm Modes
When the alarm is activated, the word Alarm appears on
the main display menu above the first button. See
Figure 4-21. Press the Alarm button to open the Reset
menu. Then press the button labeled Reset to silence
the alarm.
Reset
To Silence Alarm
B
Y
Reset Main
System Ready
LD Exer 12/14 @ 16:00
Norm 480V Emer 480V
Alarm
View Set Test
Reset
Status or Fault Description
Alarm Silenced
B
Y
Reset Main
Figure 4-21
Alarm Silence
4.4
Load Shed
(Forced Transfer to OFF)
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
DANGER
Servicing the transfer switch. Hazardous voltage will
cause severe injury or death.
Deenergize all power sources
before servicing. Turn off the main circuit breakers of all
transfer switch power sources and disable all generator sets
as follows: (1) Press the generator set off/reset button to shut
down the generator set. (2) Disconnect power to all battery
chargers. (3) Disconnect all battery cables, negative (--) leads
first. Reconnect negative (--) leads last when reconnecting the
battery cables after servicing. Follow these precautions to
prevent the starting of generator sets by an automatic transfer
switch, remote start/stop switch, or engine start command
from a remote computer. Before servicing any components
inside the enclosure: (1) Remove all jewelry. (2) Stand on a
dry, approved electrically insulated mat. (3) Test circuits with a
voltmeter to verify that they are deenergized.
The load shed (forced transfer to OFF) accessory must
be factory-installed.
The load shed accessory is
available only on programmed-transition transfer
switches. See Figure 4-22 for an illustration of the load
shed acessory.
The load shed function requires an external signal
(contact closure) to initiate transfer to the OFF position.
Connect the external contact to input #1 (if available) or
input #2 on connector TB1 on the main logic board. See
Figure 4-23. Use #12--24 AWG wire and tighten to
0.5 Nm (4.4 in. lb.).
Use the Input/Output setup menu or Kohler SiteTech
software to assign the connected input (Main Board
Input #1 or #2) to the forced transfer to off function. If the
external contact is connected to a different input
connection on an optional I/O module, assign the forced
transfer to off function to that input.
Содержание KBC
Страница 26: ...TP 6835 9 17 26 Section 2 Installation Notes...
Страница 44: ...TP 6835 9 17 44 Section 4 Communication and Accessory Connections Notes...
Страница 48: ...TP 6835 9 17 48 Section 5 Functional Tests and Setup Notes...
Страница 50: ...TP 6835 9 17 50 Section 6 Scheduled Maintenance Notes...
Страница 76: ...TP 6835 9 17 76 Section 7 Bypass Isolation and Manual Transfer Notes...
Страница 79: ......