Kohler GM87026-KP1-WHT Скачать руководство пользователя страница 2

2

TT-1622

9/16

Installation Procedure

Note:

Read all safety precautions at the beginning of

this publication before performing any work on

the generator set.

1.

Remove the generator set from service.

1.1 Press the generator set OFF/RESET button to

shut down the generator set.

1.2 Disconnect the power to the battery charger, if

equipped.

1.3 Disconnect the generator set engine starting

battery(ies), negative (--) lead first.

2.

Install the oil level indicator kit.

Note:

Apply pipe sealant to the threads of the hose

connectors.

2.1 Remove the oil drain plug and allow the oil to drain

completely. See the Service Views in the

operation manual for the oil drain location.

Note:

Dispose of all waste materials (engine oil,

fuel, filter, etc.) in an environmentally safe

manner and in accordance with all

applicable laws.

2.2 Disconnect the oil drain hose from the oil drain

valve at the oil pan. Save the oil drain valve.

2.3 Secure

the

bracket

(GM86335-WHT

or

GM86335-G49) to the service side (right-hand

side) of the skid using 2 screws (M933-10025-60)

and 2 nuts (M6923-10-80). See Figure 2 for

bracket position.

2.4 Secure the oil level gauge (227257) to the bracket

using 4 mounts (241769), 4 lock washers

(X-22-12), and 4 nuts (X-6210-2).

Note:

Use the upper set of holes in the mounting

bracket for assembly.

2.5 Install the coupling (X-567-1) into the oil gauge.

See Figure 2 for location.

2.6 Install the connector (X-582-5) into the back of the

oil level gauge.

2.7 Connect the pipe (X-209-2) to the bushing in the

oil pan.

2.8 Connect the pipe cross (X-207-7) to the pipe.

2.9 Connect the pipe plug (X-75-3) to the pipe cross

as shown in Figure 2, item 14.

2.10 Connect the hose connector (X-582-5) to the pipe

cross.

2.11 Secure the oil hose (X-422-18) to the hose

connector in the oil pan using a hose clamp

(X-426-12).

2.12 Place the restrictor plug (GM98574) in the other

end of the oil hose (X-422-18) and secure it to the

hose connector in the back of the oil gauge using a

hose clamp (X-426-12).

2.13 Cut the copper tubing at a slight angle at the

beginning of the arc. See Figure 2, item 1.

2.14 Attach one end of the hose (X-386-74) to the copper

tubing using a hose clamp (X-426-9) to secure.

Note:

Place hose clamps 6 mm (0.25 in.) from

the hose end and tighten.

2.15 Position the existing oil drain valve at the position

shown in Figure 2, item 16.

2.16 Remove the existing plate and replace with a new

cover plate (GM47418-WHT or GM47418-G49)

reusing the existing hardware.

2.17 Insert the hose connector (X-582-38) into the hole

of the coverplate.

2.18 Attach the other end of the hose (X-386-74) to the

connector using a hose clamp (X-426-9) to

secure.

3.

Replenish engine oil.

3.1 Replace the oil drain plug and refill the engine with

oil. See the operation manual for complete oil fill

instructions.

4.

Wire the oil level gauge

4.1 See Figure 4 for wiring to the oil level gauge.

Note:

Figure 4 shows a partial view of the wiring

diagram. For a complete wiring diagram, see the

generator operation manual.

4.2 If the generator set does not have a

Decision-Maker

t

3500 controller, see the

instructions supplied with the oil level gauge for

wiring the gauge to a customer-provided light or

alarm.

Содержание GM87026-KP1-WHT

Страница 1: ...pare the kit parts with the parts list at the end of this publication before beginning installation Perform the steps in the order shown Safety Precautions Observethefollowingsafetyprecautionswhileinstalling the kit Accidental starting Can cause severe injury or death Disconnect the battery cables before working on the generator set Remove the negative lead first when disconnecting the battery Rec...

Страница 2: ...bushing in the oil pan 2 8 Connect the pipe cross X 207 7 to the pipe 2 9 Connect the pipe plug X 75 3 to the pipe cross as shown in Figure 2 item 14 2 10 Connect the hose connector X 582 5 to the pipe cross 2 11 Secure the oil hose X 422 18 to the hose connector in the oil pan using a hose clamp X 426 12 2 12 Place the restrictor plug GM98574 in the other end of the oil hose X 422 18 and secure i...

Страница 3: ...0 Oil level bracket GM86335 WHT or GM86335 G49 11 Hose X 422 18 and hose clamps X 426 12 qty 2 12 Hose connector X 582 5 13 Pipe X 209 2 Attach to oil pan on engine 14 Pipe plug X 75 3 15 Pipe cross X 207 7 16 Position existing oil drain valve in this position 17 Restrictor plug GM98574 18 Hose connector X 582 5 19 Hose X 386 74 and hose clamps X 426 9 qty 2 20 Cover plate GM47418 WHT or GM47418 G...

Страница 4: ...tdown will be displayed for either low or high oil level Note For more information on SiteTecht see TP 6701t SiteTech Software Operation Manual Figure 3 Programmable Digital Input 110 Parameter in SiteTecht Parts List Oil Level Indicator Kits Kits GM87026 KP1 WHT and GM87026 KP1 G49 Qty Description Common Parts 1 Gauge oil level 227257 4 Mount controller 241769 1 Cover plate for Kit GM87026 KP1 WH...

Страница 5: ...TT 1622 9 16 5 1 Oil level gauge 1 See the full wiring diagram in the operation manual GM86969B D Figure 4 Wiring for Oil Level Gauge Typical ...

Страница 6: ...6 TT 1622 9 16 Notes ...

Страница 7: ...TT 1622 9 16 7 Notes ...

Страница 8: ...stems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone 65 6264 6422 Fax 65 6264 6455 Availability is subject to change without notice Kohler Co reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever Contact your local Kohlerr generator set distributor for availability 2014 and 2016 by Kohler Co All rights reser...

Отзывы: