Kohler GM62345 Скачать руководство пользователя страница 7

TT-1445 7/16

7

15RES(A)/R(E)YG and 30RES(A)/R(E)YG

1.

Before working on the generator set or connected
equipment, disable the generator set as follows:

a.

Press the OFF button on the generator set controller.

b.

Disconnect the power to the battery charger.

c.

Remove the battery cables, negative (--) lead first.

2. Release the retaining clips to open the housing and

then remove the air cleaner element.

3. Remove and discard the old air cleaner element.

4. Install the new element.

5. Wipe the cover and housing with a clean rag. Make

sure the sealing surfaces fit correctly and reattach

the retaining clips.

6. Reconnect the battery cable, negative (--) lead last.

GM21379

1. Cover

2. retaining clip(s)

3. Housing

4. Pressure tap (1/8--27 NPT)

5. Primary element

6. Dust ejector

1

2

3

5

6

4

Figure 9

Air Cleaner; 15RES(A)/R(E)YG, and

30RES(A)/R(E)YG

24RCL, 30RCL, 38RCLB, 48RCLA, and 60RCL

1.

Before working on the generator set or connected
equipment, disable the generator set as follows:

a.

Press the OFF button on the generator set controller.

b.

Disconnect the power to the battery charger.

c.

Remove the battery cables, negative (--) lead first.

2. Release the retaining clips to open the housing and

then remove the air cleaner element.

3. Remove and discard the old air cleaner element.

4. Install the new element.

5. Wipe the cover and housing with a clean rag. Make

sure the sealing surfaces fit correctly and reattach

the retaining clips.

6. Reconnect the negative battery cable and spark

plug lead(s).

GM90280

1. Cover

2. retaining clip(s)

3. Housing

4. Primary element

5. Dust ejector

1

2

3

4

5

Figure 10

Air Cleaner; 24/30/60RCL, 48RCLA, and

38RCLB

Содержание GM62345

Страница 1: ...r sets listed in Figure 1 Read the entire installation procedure before beginning installation Perform the steps in the order shown Generator Set Service Kit Number Sales Kit Number 8RESV L GM90365 GM...

Страница 2: ...ner A sudden backfire can cause severe injury or death Do not operate the generator set with the air cleaner removed Hot engine oil Can cause severe injury or death Avoid skin contact with hot oil Do...

Страница 3: ...a drain pan The tube will reduce the potential for spilled oil c Open the oil drain valve on the engine d Remove the dipstick and oil fill cap Allow time for the engine oil to drain completely e Clos...

Страница 4: ...eler gauge See Figure 4 Adjust the gap by carefully bending the ground electrode See Figure 3 5 For easy removal apply a light coating of anti seize lubricantto the sparkplug threads Wipe away any exc...

Страница 5: ...ct the battery cable negative lead last 1 2 3 4 5 6 7 586536 1 Cover knob 2 Air cleaner cover 3 Element cover nut 4 Element cover 5 Foam precleaner 6 Air cleaner element 7 Air cleaner base Figure 5 Ai...

Страница 6: ...t 3 Base 4 Blower housing 5 Air cleaner cover 2 3 1 4 5 Figure 7 Air Cleaner 10 12RESV L 17 18RES L 20RES A AL B C CL D L 1 Before working on the generator set or connected equipment disable the gener...

Страница 7: ...tap 1 8 27 NPT 5 Primary element 6 Dust ejector 1 2 3 5 6 4 Figure 9 Air Cleaner 15RES A R E YG and 30RES A R E YG 24RCL 30RCL 38RCLB 48RCLA and 60RCL 1 Before working on the generator set or connect...

Страница 8: ...s negative lead first 2 Remove the wing nut and remove the air cleaner retaining plate 3 Remove and discard the old air cleaner element 4 Install the new element 5 Wipe the cover and housing with a cl...

Отзывы: