TT-1379
5/16
3
Installation Procedure
1.
Remove the generator set from service.
1.1
For generator sets with an ADC 2100
controller:
Place the generator set master
switch in the OFF position.
For generator sets with an ADC II or ADC IId
controller:
Press the start/stop button to stop
the generator set. Then, press the power button
to turn off the controller.
For generator sets with a Decision-Maker
r
3500 controller:
Press the OFF/RESET button
to shut down the generator set.
1.2
Disconnect the generator set engine starting
battery, negative (--) lead first.
2.
Install the remote digital gauge.
2.1
Select a dry location to mount the remote digital
gauge.
Consider the length of the wiring
harness and the gauge’s mounting depth and
size when selecting a location. See Figure 5 for
the mounting dimensions.
2.2
For units with an
ADC controller
, order a remote
extension harness kit. See Figure 3 for kit
selection. Do not use more than 3 remote
harness kits and do not exceed 23 m (75 ft.) in
harness length.
Remote Extension
Harness Kit Number
Length
m (ft.)
As
Shown In
GM32333-KP1
4.6 (15)
Figure 8
GM32333-KP2
7.6 (25)
Figure 3
Remote Extension Harness Kits (For Units
with an ADC Controller)
For units with a
Decision-Maker
r
3500
controller
, order a remote extension harness
kit. See Figure 4 for kit selection.
DO NOT
exceed 91.4 m (300 ft.) CAN network length.
Remote Extension
Harness Kit Number*
Length
m (ft.)
As
Shown In
GM91774-KP1
7.6 (25)
Figure 11
GM91774-KP2
15.2 (50)
GM91774-KP3
30.5 (100)
GM92053-KP1
7.6 (25)
Figure 12
GM92053-KP2
15.2 (50)
GM92053-KP3
30.5 (100)
* Y Harness shown in Figure 13
Figure 4
Remote Extension Harness Kits (For Units
with a Decision-Maker
r
3500 Controller)
GM30565-B
NOTE: Dimensions in brackets
are inch equivalents.
Figure 5
Mounting Dimensions
2.3
Connect the 6-pin inline connector of the gauge
harness (GM32325 or GM100955) to the 6-pin
inline connector on the digital gauge. See
Figure 6 and Figure 7 or Figure 10.
2.4
For Kit GM32337-KP1:
Connect the 12-pin
connector end of the gauge harness or a remote
extension harness to the generator set’s
customer-interface 12-pin connector.
See
Figure 7, Figure 8, and Figure 9.
2.5
For Kit GM100956-KP1:
Connect the 6-pin
connector end of the gauge harness to a remote
extension harness. See Figure 10, Figure 11,
Figure 12, Figure 13, Figure 14, and Figure 15.
Connect the lead ends of the extension harness
to the TB12 terminal strip. The TB12 terminal
strip is located inside the junction box. See
Figure 15 for TB12 connections.