Kohler GM100956-KP1 Скачать руководство пользователя страница 3

TT-1379

5/16

3

Installation Procedure

1.

Remove the generator set from service.

1.1

For generator sets with an ADC 2100

controller:

Place the generator set master

switch in the OFF position.

For generator sets with an ADC II or ADC IId

controller:

Press the start/stop button to stop

the generator set. Then, press the power button

to turn off the controller.

For generator sets with a Decision-Maker

r

3500 controller:

Press the OFF/RESET button

to shut down the generator set.

1.2

Disconnect the generator set engine starting

battery, negative (--) lead first.

2.

Install the remote digital gauge.

2.1

Select a dry location to mount the remote digital

gauge.

Consider the length of the wiring

harness and the gauge’s mounting depth and

size when selecting a location. See Figure 5 for

the mounting dimensions.

2.2

For units with an

ADC controller

, order a remote

extension harness kit. See Figure 3 for kit

selection. Do not use more than 3 remote

harness kits and do not exceed 23 m (75 ft.) in

harness length.

Remote Extension

Harness Kit Number

Length

m (ft.)

As

Shown In

GM32333-KP1

4.6 (15)

Figure 8

GM32333-KP2

7.6 (25)

Figure 3

Remote Extension Harness Kits (For Units

with an ADC Controller)

For units with a

Decision-Maker

r

3500

controller

, order a remote extension harness

kit. See Figure 4 for kit selection.

DO NOT

exceed 91.4 m (300 ft.) CAN network length.

Remote Extension

Harness Kit Number*

Length

m (ft.)

As

Shown In

GM91774-KP1

7.6 (25)

Figure 11

GM91774-KP2

15.2 (50)

GM91774-KP3

30.5 (100)

GM92053-KP1

7.6 (25)

Figure 12

GM92053-KP2

15.2 (50)

GM92053-KP3

30.5 (100)

* Y Harness shown in Figure 13

Figure 4

Remote Extension Harness Kits (For Units

with a Decision-Maker

r

3500 Controller)

GM30565-B

NOTE: Dimensions in brackets

are inch equivalents.

Figure 5

Mounting Dimensions

2.3

Connect the 6-pin inline connector of the gauge

harness (GM32325 or GM100955) to the 6-pin

inline connector on the digital gauge. See

Figure 6 and Figure 7 or Figure 10.

2.4

For Kit GM32337-KP1:

Connect the 12-pin

connector end of the gauge harness or a remote

extension harness to the generator set’s

customer-interface 12-pin connector.

See

Figure 7, Figure 8, and Figure 9.

2.5

For Kit GM100956-KP1:

Connect the 6-pin

connector end of the gauge harness to a remote

extension harness. See Figure 10, Figure 11,

Figure 12, Figure 13, Figure 14, and Figure 15.

Connect the lead ends of the extension harness

to the TB12 terminal strip. The TB12 terminal

strip is located inside the junction box. See

Figure 15 for TB12 connections.

Содержание GM100956-KP1

Страница 1: ...of the remote digital gauge s start stop function requires that the jumper is enabled on the Advanced Digital Control ADC generator sets shipped from the factory already have the jumper enabled Refer to the wiring diagram in the generator set operation manual if the jumper was disconnected from terminals 1 and 2 on the P7 connector continuous power mode Note For generator sets with an ADC 2100 con...

Страница 2: ...fainting or death Carbon monoxide is a poisonous gas present in exhaust gases Carbon monoxide is an odorless colorless tasteless nonirritating gas that can cause death if inhaled for even a short time Carbon monoxide poisoning symptoms include but are not limited to the following D Light headedness dizziness D Physical fatigue weakness in joints and muscles D Sleepiness mental fatigue inability to...

Страница 3: ... Kits For Units with an ADC Controller For units with a Decision Makerr 3500 controller order a remote extension harness kit See Figure 4 for kit selection DO NOT exceed 91 4 m 300 ft CAN network length Remote Extension Harness Kit Number Length m ft As Shown In GM91774 KP1 7 6 25 Figure 11 GM91774 KP2 15 2 50 GM91774 KP3 30 5 100 GM92053 KP1 7 6 25 Figure 12 GM92053 KP2 15 2 50 GM92053 KP3 30 5 1...

Страница 4: ...ects to the remote digital gauge connector Connects to the generator set customer interface connector or a remote harness connector Figure 7 Remote Gauge Harness GM32325 Included with Kit GM32337 KP1 GM30248 15 ft Extension Harness Kit GM32333 KP1 25 ft Extension Harness Kit GM32333 KP2 Figure 8 Remote Extension Harness Kits For Use With Kit GM32337 KP1 GM33846A D Figure 9 Harness Connection Diagr...

Страница 5: ...M91774 KP2 100 ft Extension Harness Kit GM91774 KP3 Figure 11 Remote Extension Harness Kits For Use With Kit GM100956 KP1 GM100997 25 ft Extension Harness Kit GM92053 KP1 50 ft Extension Harness Kit GM92053 KP2 100 ft Extension Harness Kit GM92053 KP3 Figure 12 Remote Extension Harness Kits For Use With Kit GM100956 KP1 GM100996 Y Harness Kit GM92054 KP1 Figure 13 Y Harness Kit For Use With Kit GM...

Страница 6: ...6 TT 1379 5 16 GM88254 B Sheet 1 of 2 Sheet 2 of 2 Figure 15 Interconnection Diagram For Kit GM100956 KP1 ...

Страница 7: ...he controller may automatically power down and go into Sleep Mode to conserve battery power This will occur after one hour of inactivity only when the CAN parameter is set to Cn06 If the CAN parameter is set to Cn01 the controller will remain powered and will draw battery power See TT 1364 for more information ADC 2100 Controller CAN Setting Power Down Time Application Notes Cn01 Never None J1939 ...

Страница 8: ...s until the gauge beeps and the display changes 6 Use the UPorDOWNbuttonsto selecteither Intor USA units 7 Press and hold both the UP and DOWN buttons until the gauge beeps and the display changes 8 Press the DOWN button 9 The gauge displays ESC 08 10 Press and hold both the UP and DOWN buttons until the gauge switches to the monitor mode GM30565 B 1 Fault indicator 2 Arrow if blinking indicates t...

Страница 9: ...the AUTO position for remote start stop If the ADC 2100 master switch is in the RUN position a remote stop command will not stop the generator set The arrow at the top left side of the display blinks to indicate that the generator set is running see Figure 17 item 2 Note The ADC II and ADC IId must be powered display active for remote start stop Note The Decision Maker 3500 must be powered display...

Страница 10: ...uency LB Low Battery Voltage HB High Battery Voltage Figure 19 Fault Codes Displayed on the Gauge for Units Equipped with an ADC 2100 Controller Units with ADC II or ADC IId Controller Digital Gauge Display Description LOP Low Oil Pressure OC Over Crank OS Over Speed AF Auxiliary Input Fault HE High Engine Temperature OU Over Voltage UU Under Voltage OF Over Frequency UF Under Frequency LB Low Bat...

Страница 11: ...TT 1379 5 16 11 Notes ...

Страница 12: ...s Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone 65 6264 6422 Fax 65 6264 6455 Availability is subject to change without notice Kohler Co reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever Contact your local Kohlerr generator set distributor for availability 2004 2006 2012 and 2016 by Kohler Co All rights...

Отзывы: