Section 4 Troubleshooting
TP-6844 1/13
4.10 Controller Troubleshooting
Refer to the controller troubleshooting table in
Figure 4-5 when troubleshooting procedures in
Section 4.9 indicate a possible controller problem.
Also check the controller display for fault messages
and see Section 4.7, Fault Messages.
Always check the controller settings before replacing
the controller. VSC controller settings can be checked
and adjusted through the controller’s user interface or
using a personal computer and Kohler SiteTech
software. The generator set operation manual
contains the instructions for checking and changing
the controller settings. See TP-6701, SiteTech
Software Operation Manual. Kohler SiteTech software
is available to authorized distributors and dealers.
Figure 4-5
Figure 4-5
VSC Controller Troubleshooting
Problem
Possible Cause
Corrective Action
Reference
Controller LCD
display is off.
Low or no battery voltage
Check controller connections.
W/D Section 7
Check DC power to the VSC
controller.
Check generator set battery
connections and condition.
Check power connection to the
generator set terminal block
(power for battery charging). (if
equipped)
Controller display
backlight is off.
Backlight turns off after about
1 minute with no activity
Backlight will turn on when a
button is pressed or the
generator set starts.
—
Loss of
communication to
accessory modules.
Bad connections
Check wiring and connections.
Verify that cable size and length
of run comply with the
instructions in the Installation
Manual.
Generator set Installation
Manual or accessory module
documentation
Communication cable does not
meet required specifications
Use shielded, twisted-pair cable
as specified in the Installation
Manual. Do not exceed the
maximum cable lengths given in
the Installation Manual.
Installation Manual
Low or no battery voltage
Check generator set battery
connections and condition.
—
See “Low or no battery voltage”
above.
Date is flashing.
Controller power was
disconnected and then
reconnected
Check battery connections.
Check controller connections.
W/D Section 7
Check power connection to the
generator set terminal block.
Reset the time, date, and
exercise schedule.
Generator set O/M
Cannot change input
and output settings.
Controller is set up for the optional
communications kit, which locks
the input and output settings.
For a generator set with a
communications kit, no action is
needed. Inputs and outputs are
not adjustable.
If the generator set is connected
to a PIM, use SiteTech to
change the Personality Installed
Option parameter setting.
Содержание 6VSG
Страница 1: ...Service TP 6844 1 13a DC Generator Sets Models 6VSG 24VDC 36VDC 48VDC Controller VSC...
Страница 12: ...12 Service Assistance TP 6844 1 13 Notes...
Страница 26: ...26 Section 2 Scheduled Maintenance TP 6844 1 13 Notes...
Страница 50: ...50 Section 3 Controller TP 6844 1 13 Notes...
Страница 84: ...84 Section 5 Component Testing and Adjustment TP 6844 1 13 Notes...
Страница 90: ...90 Section 6 Disassembly Reassembly TP 6844 1 13 Notes...
Страница 92: ...92 Section 7 Drawings and Diagrams TP 6844 1 13 Figure 7 2 Figure 7 2 Dimension Drawing ADV 8060 Sheet 1...
Страница 93: ...TP 6844 1 13 Section 7 Drawings and Diagrams 93 Figure 7 3 Figure 7 3 Dimension Drawing ADV 8060 Sheet 2...
Страница 94: ...94 Section 7 Drawings and Diagrams TP 6844 1 13 Figure 7 4 Figure 7 4 Dimension Drawing ADV 8060 Sheet 3...
Страница 96: ...96 Section 7 Drawings and Diagrams TP 6844 1 13 Figure 7 6 Figure 7 6 Schematic Diagram 24V ADV 8460 Sheet 2...
Страница 107: ......