8. Operation 

In order to initialise the inductive switch function, it is essential that the float activates the contact 
once in each direction. 

Adjustment of limit-values 
The switch-point can be adjusted to the desired levels by using. 

Reference edge:

 approx. the middle of the sensor. 

Slide the switch housing up or down until the reference edge coincides with the desired 
switch-point scale reading. 

Overranging 

With non-pulsating flow, the maximum flow rate can be exceeded. Only an increase in pressure 
loss will result (max. permissible operating pressure must not be exceeded!) 

9. Maintenance 

If the medium to be measured is clean, the series URL is virtually maintenance- free. If deposits 
form on the inner housing or parts, periodic cleaning of the unit is recommended. Remove the 
units from the piping with a suitable tool; clean the flow meter with a suitable cleaning agent or 
make use of an ultrasonic bath. 

 

 

10. Technical information 

Installation position: 

vertical (flow from bottom to top) 

Accuracy class:  

4 according to VDI 

Max. temperature:  

100°C (65°C for PVC) 

Max. pressure:  

03H…23H; 16 bar (with PN 16 flange) 

 

25H…33H; 12 bar (with PN 16 flange) 

 

35H…41H; 8 bar (with PN 16 flange) 

 

01L…23L; 16 bar (with PN 16 flange) 

 

25L…33L; 10 bar (with PN 16 flange) 

 

in all other cases 6 bar 

Calibration conditions: 
 

water:  

20°C, air: 20°C, 

 

air pressure: 

1.013 bar abs. 

Contact (optional):  

proximity switch: PNP 

 

open collector, n/o contact 

Supply voltage:  

12…24 VDC 

Current consumption:  

max. 10 mA  

Cable: 

2 m, PVC-insulated 

Ambient temperature:  

-25…+70°C 

Protective category:  

IP 67 

Содержание URK series

Страница 1: ...Operating instructions for Variable area flow meter Model URK...

Страница 2: ...4 9 Maintenance 5 10 Technical information 5 11 Order codes 6 12 Dimensions 7 13 EU Declaration of conformance 8 Manufactured by Sold by Kobold Unirota Ltd Kobold Messring GmbH 4400 Ny regyh za Nordri...

Страница 3: ...E mark pipeline filled with gas liquids group 2 group 1 group 2 table 7 table 8 table 9 3 Instrument inspection Instruments are inspected before shipping and sent out in perfect condition Should damag...

Страница 4: ...glass which optically allows direct flow observation 6 Mechanical connection Before Installation Remove all transportation safety locks and ensure that no packing material remains within the unit Be...

Страница 5: ...ly maintenance free If deposits form on the inner housing or parts periodic cleaning of the unit is recommended Remove the units from the piping with a suitable tool clean the flow meter with a suitab...

Страница 6: ...15H 16 160 15L 0 5 5 28 F6 DN 25 B5 DN 20 B6 DN 25 A6 1 A7 1 17H 25 250 17L 0 8 8 28 19H 40 400 19L 1 3 13 36 21H 63 630 21L 2 0 20 34 23H 100 1 000 23L 3 2 32 43 25H 160 1 600 25L 5 50 48 F7 DN 32 B...

Страница 7: ...110 1 127 0 98 6 URK 9x 410 50 140 110 165 125 2 152 0 120 7 URK Ax 550 65 160 130 185 145 2 177 8 139 7 URK Bx 560 80 190 150 200 160 3 190 5 152 4 Material combination URK Ordering code Connection...

Страница 8: ...ial EN 55011 2009 A1 2010 ISM ratio frequency equipment EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements EN 61010 1 2011 Safety requirements for electri...

Отзывы: