PDD
Page 14
PDD K04/0217
10.4. Switching
behaviour
The following diagram clarifies the switching behaviour of the pressure switch.
The contact closes (type of contact: N.O.) when exceeding the switch point or
falling short of the window point. It opens only again after exceeding the window
point plus the hysteresis or falling below the switch point minus the hysteresis. An
LED signals the switching status of the pressure switch.
time/ t
Display
bar (°C)
Switching pt.
Hysteresis
LED ON
time / t
Display
bar (°C)
Switching pt.
Hysteresis
LED ON
Hysteresis
Window point
LED ON
only PDD-1 and PDD-2