Kobold NEK Series Скачать руководство пользователя страница 6

NEK 

Seite 6 

 

NEK K05/0516 

9. Maintenance 

The Conductive Level Switch is maintenance-free. 
Should the electrodes be contaminated with a non-conductive coating (oil, 
grease, etc.), they can be cleaned with a suitable tool (e.g. cloth). Do not use a 
cleaner that would damage the plastic housing. 

 
 
 

10. Technical Information 

Case:  

PPS (Rhyton) or polypropylene 

Electrodes:  

stainless steel 1.4571 

Connections:  

R 3/4 or 3/4 NPT male thread 

Operating temperature: 

-25 to +85 °C (PPS) 

 

-25 to +60 °C (polypropylene) 

Max. pressure:  

20 bar (PPS) 

 

6 bar (polypropylene) 

Installation position:  

horizontal or vertical 

Contact components:  

open collector (NPN or PNP) 

 wet 

signal 

 Option: 
 

relay (floating changeover contact) 

Electrical connection:  

2 m encapsulated cable 

 

3-core screened (open collector) 

 

5-core unshielded (relay) 

Supply:  

18-29 V

DC

 < 20 mA 

Switch-in delay:  

dry/wet: 0.5 sec. 

 

wet/dry: 0.5 sec. 

Sensitivity:  

approximately 50 k

 

Min. Conductance:  

approximately 100 µS/cm 

Switch capacity:  

open collector:

 

 

max. 32 V / max. 100 mA / short-circuit-proof 

 

Relay: 

 

max. 1 A / 30 V / short-circuit-proof 

Protection type:  

IP 68 

 
 
 

Содержание NEK Series

Страница 1: ...Operating Instructions for Conductive Level Switches Model NEK...

Страница 2: ...nection 4 7 1 General 4 7 2 NPN switching output NEK 1 5 7 3 PNP switching output NEK 2 5 7 4 Relay switching output NEK 3 5 8 Commissioning 5 9 Maintenance 6 10 Technical Information 6 11 Order Codes...

Страница 3: ...3 Instrument Inspection Instruments are inspected before shipping and sent out in perfect condition Should damage to a device be visible we recommend a thorough inspection of the delivery packaging In...

Страница 4: ...operate on the conductive principle of measurement The conductive medium touches both electrodes causing a negligible alternating current to flow the output state changes 6 Mechanical Connection 6 1...

Страница 5: ...8 Commissioning The measuring instruments are pre set and are ready for operation after electrical connection The LED signals the switch state of the level switch LED off no power supply LED off with...

Страница 6: ...ating temperature 25 to 85 C PPS 25 to 60 C polypropylene Max pressure 20 bar PPS 6 bar polypropylene Installation position horizontal or vertical Contact components open collector NPN or PNP wet sign...

Страница 7: ...NEK NEK K05 0516 Seite 7 11 Order Codes Example NBK 1136 R20 C 12 Dimensions...

Страница 8: ...ards Emission standard for industrial environments EN 61000 6 2 2006 03 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments EN 61010 1 2011 07 Safety requ...

Отзывы: