KEC
‐
Soft
KEC
K01/0217
page
13
2.4
Settings
4
‐
20
mA
The
Flow
‐
sensor
has
one
4
‐
20
mA
analogue
output(s),
optional
2x
4…20mA
analogue
outputs.
The
outputs
are
individual
adjustable.
2.4.1
4
‐
20
mA
(analogue
output
settings)
You
can
enter
your
desired
measuring
outputs
at
"Value".
Please
enter
also
the
correct
units
for
your
needs
at
"Unit".
Your
upper
limit
value
will
be
the
measuring
limit
of
the
value
that
was
set
at
"Value",
if
you
choose
"Autoscale".
Please
insert
your
specific
limits
at
"Scale
4mA/Scale
20mA"
if
you
want
to
scale
manually.
You
can
also
enter
adjustments
for
"Channel
2",
if
the
sensor
is
equipped
with
2
channels.
It
is
possible
to
set
different
scenarios
in
case
of
an
error
at
"Error
Behaviour".
Stay
at
NAMUR
limits:
Depending
on
the
measuring
value
the
output
will
be
set
3,8
mA
or
20,5
mA.
Error
=
22
mA:
The
output
current
will
be
set
to
22
mA.
Error
=
2
mA:
The
output
current
will
be
set
to
2
mA.