Stand by time:
max. 13 s
Temperature range:
-25... +80 °C
Top hat rail mounting:
DIN EN 50022 and DIN 46277
Housing protection:
IP 40
Terminal protection:
IP 20
Material
Polycarbonat
Sensor output:
Short-circuit proof
Cable break or short circuit:
Recognised as break in flow,
Flow LED will flash.
Power failure:
Calibration data retained for 10 years
No Battery
Trend display
approx. 10%
Consistency:
ca. 1%
Reaction time:
generally 5 sec., max 12 sec.
Accuracy of temperature limit: ± 2 °C
14. Order Codes