background image

KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205

Phone (412) 788-2830 • Fax (412)-788-4890

KOBOLD KAL-L (KAL-8000 Series)

Thermal Air Flow Switch

User Instructions

Manual-KAL-L_5-12

Содержание KAL-8115

Страница 1: ...KOBOLD Instruments Inc 1801 Parkway View Drive Pittsburgh PA 15205 Phone 412 788 2830 Fax 412 788 4890 KOBOLD KAL L KAL 8000 Series Thermal Air Flow Switch User Instructions Manual KAL L_5 12...

Страница 2: ......

Страница 3: ...5 4 0 Electrical Connections 5 5 0 Operation 6 5 1 Flow Setpoint Adjustment 6 5 2 Adjustment of the Start up Time Delay 8 6 0 Maintenance 9 7 0 Need Help with Your KAL L Flow Switch 9 List of Diagram...

Страница 4: ......

Страница 5: ...red flow value drops below the setpoint value an output relay is activated providing an alarm or control input 2 0 Specifications Switching Range 3 3 to 66 feet second 68 F 14 5 PSIA Restricted span f...

Страница 6: ...KAL L 2 FM Rev 5 17 12 7 0 4 0 15 5mm 4 3 PG 13 5 Hex 41mm Diagram 2 1 Dimensions All dimensions in inches Unless otherwise noted HVAC Duct Mount Flange 1 2 NPT Compression Fitting Cable Gland...

Страница 7: ...to the flow stream a notch has been placed on the probe hex nut to aid in alignment For optimal results the probe should be installed so that the notch is aligned directly over the centerline of the p...

Страница 8: ...unit in the pipe upper hemisphere Liquid and sediment which settle at the bottom cannot cause measuring errors C L Mount probe such that the notch cut into the hex is perpendicular to the pipe centerl...

Страница 9: ...applications where adding an NPT connection is impractical 3 3 2 Prior to installing the flange the flange face which contacts the surface of the HVAC duct should be sealed using a field manufactured...

Страница 10: ...the third LED on the indicator bar The third LED is wired to flash permanently to allow users to judge the location of the flow setpoint relative to system flow The flow switch point is set by adjust...

Страница 11: ...LED which is flashing At this point the DUO LED turns red and the relay switches over The KAL L is now adjusted at the desired setpoint 5 1 2 4 Adjust system flow to normal 5 1 3 Adjustment of Precis...

Страница 12: ...rend indicator LEDs are lit As the trend indicator span is adjusted past the third LED which is flashing note that the DUO LED changes from red to green and the relay switches over 5 1 4 4 The KAL L i...

Страница 13: ...egraded performance For this reason we strongly recommend that the proper filtration be installed in the system It is also recommended that the KAL L be occasionally removed from the system and its me...

Страница 14: ......

Страница 15: ...v 5 17 12 CAUTION PLEASE READ THE FOLLOWING WARNINGS BEFORE ATTEMPTING INSTALLATION OF YOUR NEW DEVICE FAILURE TO HEED THE INFORMATION HEREIN MAY RESULT IN EQUIPMENT FAILURE AND POSSIBLE SUBSEQUENT PE...

Страница 16: ...e national state and local codes Temperature and Pressure The KAL K is designed for use in application temperatures from 10 to 250 F and for use at pressures up to 115 PSIG Operation outside these lim...