...C3...
...C3... K01/0916
Seite 11
Filter
The filter function "
Filt
" generates the sliding average value from the measured
values. The following values are available (see section 6.2 Settings):
1 / 2 / 4 / 8 / 16 / 32 / 64
The filter value determines the dynamic behaviour of the indicated value: high
values result in a slow display response. The filter is disabled if a filter value of "1"
is selected. In other words, the indicated value is equal to the unfiltered measured
value.
The integrated step detector responds to a measured-value step change greater
than approximately 6.25% of the upper range value. When a measured-value
step change is detected, the actual measured value is displayed immediately.
Contact Model
The function of the transistor switching output is set in menu item "
Con, Co1 or
Co2
". The switching function switches from
no - N/O contact
to
nc - N/C
to
Fr – frequency
(Con and Co1 only and
for sensors with impulse
output)
and back.
N/O contact means: contact closes when switching point is exceeded
N/C means: contact opens when switching point is exceeded
Frequency means: frequency output synchronized with vane frequency
Current output
The current output is selected in menu items
"
S-C
" Start current indicated value < > 0(4) mA
"
E-C
" End current indicated value < > 20 mA
"
SCS
" Start current selection (0-20 mA or 4-20 mA).
The indicated value at which 0(4) mA flow is entered in menu item Start current.
The indicated value at which 20 mA flow is entered in menu item End current.
Change Code
The change code option "
CCo
" secures the unit against unauthorised tempering.
If the code is different from 000, the user must input the code immediately after
entering the adjustment mode.