Dimming actuator 1-gang 200 W with binary input, 3-gang

4.1 Fitting and electrical connection

 DANGER!

When connecting the bus/extensions and mains voltage wires in a shared appliance
box, the KNX bus line may come into contact with the mains voltage.

This endangers the safety of the entire KNX installation. People at remote devices
may also receive an electric shock.

Do not place bus/extensions and mains voltage terminals in a shared connection
compartment. Use an appliance box with a fixed partition wall or separate appliance
boxes.

Connecting and fitting the device

In secure operation (preconditions):

Secure commissioning is activated in the ETS.

Device certificate entered/scanned or added to the ETS project. A high resolution camera
should be used to scan the QR code.

Document all passwords and keep them safe.

Mounting in suitable appliance box (recommendation: electronic device box with partition). Ob-
serve cable routing and spacing (Figure 3)!

Figure 3: Mounting example in electronic device box with partition wall, series push-button and

NTC temperature sensor

(5)

Appliance box

(6)

Partition

(7)

potential-free contacts (e.g. series push-button)

(8)

NTC temperature sensor (optional)

4 / 10

82404402

02.02.2021

Содержание 506500

Страница 1: ...f at least 4 mm must be maintained between bus conductors and mains voltage cores Danger of electric shock on the KNX installation Do not connect any external voltage to the in puts The device might be damaged and the SELV potential on the KNX bus line will no longer be available Fire hazard For operation with inductive transformers each transformer must be fused on the primary side in accordance ...

Страница 2: ...offers protection against manipula tion in building automation and can be configured in the ETS project Detailed specialist know ledge is required A device certificate which is attached to the device is required for safe com missioning During mounting the certificate must be removed from the device and stored se curely Planning installation and commissioning of the device are carried out with the ...

Страница 3: ...ery state Operation of the output via extension inputs 1 and 2 possible with existing supply via KNX Flickering of the connected lamps due to undershoot of the specified minimum load or through centralised pulses from the power stations This does not represent any defect in the device Characteristics extension inputs Switching operating function Dimming operating function incl colour temperature d...

Страница 4: ...on wall or separate appliance boxes Connecting and fitting the device In secure operation preconditions Secure commissioning is activated in the ETS Device certificate entered scanned or added to the ETS project A high resolution camera should be used to scan the QR code Document all passwords and keep them safe Mounting in suitable appliance box recommendation electronic device box with partition...

Страница 5: ... removed from the device and stored securely The COM reference potential must not be connected together with COM connections of other devices 4 2 Commissioning Commissioning the device In the as delivered state the actuator is passive i e no telegrams are transmitted to the KNX The output is set to the universal dimming principle with automatic recognition of the load type Control of the output is...

Страница 6: ...lashing slowly The safe state mode is activated With a new brief press of the programming button the programming mode can be switched on and off as usual also in the safe state mode If Programming mode is active the programming LED stops flashing Deactivating safe state mode Switch off bus voltage wait approx 10 s or carry out ETS programming Master reset The master reset restores the basic device...

Страница 7: ...X 5 18 mA Connection mode KNX Connection terminal on control cable Output Connection mode Screw terminals Rated voltage AC 230 240 V Connected load depends on the connected lamps and set load type Figure 6 and Figure 7 ETS parameter load type UNI universal with automatic calibration procedure LJ conv transformer inductive leading edge phase control LED leading edge phase control dž electr transforme...

Страница 8: ...ength of extension unit cable max 10 m Cable type preferably J Y St Y Poll voltage extension inputs approx 5 V 6 Troubleshooting Connected LED lamps or compact fluorescent lamps switch off in the lowest dimming position or flicker The set minimum brightness is too low Increase minimum brightness Connected LED lamps or compact fluorescent lamps flicker Cause 1 Lamps are not dimmable Check manufactu...

Страница 9: ...ailing edge phase control Check the operation in the HV LED leading edge phase control setting reduce the connected load as well if necessary Exchange lamps for another type The response of the surge protection can be signalled by sending a short circuit telegram or can be determined by polling the short circuit communication object Cause 3 short circuit in output circuit Disconnect the output fro...

Страница 10: ...another type of LED lamp or an LED lamp of another manufacturer 7 Accessories Remote sensor NTC temperature sensor 1493 00 Condensation sensor 5069 00 Leakage sensor 5068 00 8 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade Please submit or send faulty devices postage paid together with an error description to your re sponsible salesperson speci...