background image

•  Provide power to the required point of installation. Suitable IP rated junction boxes should be used 

where required

• Ensure the power source is via an RCD or an RCBO
• Connect the mains supply, Live (brown), Neutral (blue) and Earth (green/yellow) (see Fig 3)

• The power source connections should be local and accessible via a suitable IP rated enclosure
• Avoid installing in areas where water will sit on top of the fitting for long periods of time (see Fig 4)

•  Ensure a minimum of 300mm drainage is put 

in below the luminaire (see Fig 4).  Note: the 
drainage below the luminaire should be able to 
drain the water away within 30 minutes

•  Ensure there is enough cable below the fitting in 

order to carry out maintenance work. The final 
circuit connection should also be accessible  
(see Fig 4, Fig 5 and Fig 6)

•  Switch on the power and test for correct 

operation

Fig 3

 

 

Connect the mains supply, Live (brown), Neutral (blue) and Earth (green/yellow) (see Fig 3) 

 

 

 

 

 

 

 

 

 

 

 

 

Fig 3 

 

The power source connections should be local and accessible via a suitable IP rated enclosure 

 

Avoid installing in areas where water will sit on top of the fitting for long periods of time (see Fig 4) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  

 

300mm 

minimum 

drainage 

required 

Loop cable to 

allow for 

maintenance 

Pea shingle or 

gravel for 

drainage 

230V AC 

Mounting 

Sleeve 

Fig 4

 

Fig 5

 

Avoid installing 

in areas with 

likelihood of 

flooding or 

standing water

 

300mm 

minimum 

drainage 

required 

Live (brown) 

Earth (green/yellow) 

Neutral (blue) 

 

 

Connect the mains supply, Live (brown), Neutral (blue) and Earth (green/yellow) (see Fig 3) 

 

 

 

 

 

 

 

 

 

 

 

 

Fig 3 

 

The power source connections should be local and accessible via a suitable IP rated enclosure 

 

Avoid installing in areas where water will sit on top of the fitting for long periods of time (see Fig 4) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  

 

300mm 

minimum 

drainage 

required 

Loop cable to 

allow for 

maintenance 

Pea shingle or 

gravel for 

drainage 

230V AC 

Mounting 

Sleeve 

Fig 4

 

Fig 5

 

Avoid installing 

in areas with 

likelihood of 

flooding or 

standing water

 

300mm 

minimum 

drainage 

required 

Live (brown) 

Earth (green/yellow) 

Neutral (blue) 

Fig 4

Fig 5

Fig 6

3

Отзывы: