Installation & Operation Manual
30
6
Hydronic piping
0
5
10
15
20
25
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
80
105
150
210
285
Flow Rate (GPM)
Pressure Drop vs. Flow (Includes Secondary Piping)
Pressure Drop (Feet of Head)
Figure 6-3
Pressure Drop vs. Flow
20°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
80
7.5
24
1"
UP26-96F/
UPS26-99F
0011
NRF-36
E7
105
9.8
27
1"
UPS26-99F
0013
NRF-36
E11
150
14.0
20
1"
UPS26-99F
0011
NRF-36
E7
210
19.6
29
1"
UPS32-160
1400-50
PL-55
E9
285
26.5
15
1-1/4"
UPS32-80
1400-20
PL-36
E11
Table 6A
Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
25°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
80
5.9
15.0
1"
UPS15-58FC
0014
PL-30/NRF-36
E7
105
7.7
17.5
1"
UP26-64F/
UPS26-99F
0014
PL-30/NRF-36
E7
150
11.0
12.8
1"
UP26-64F/
UPS26-99F
0014
PL-30/NRF-36
E7
210
15.5
19.0
1"
UP26-99F/
UPS26-99F
0013
PL-36/NRF-36
E7
285
21.0
11.5
1-1/4"
UP26-99F/
UPS26-99F
0011
PL-36/NRF-36
E7
Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude models.
NOTICE
35°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
80
4.2
7.3
1"
UPS15-58FC
007
NRF-22
Astro-30
105
5.5
9.3
1"
UPS15-58FC
007
NRF-22
Astro-30
150
7.9
9.5
1"
UPS15-58FC
008/0010
PL-30/NRF-36
Astro-30
210
11.0
9.1
1"
UPS15-58FC
0010
PL-30/NRF-36
Astro-50
285
15.0
7.3
1-1/4"
UP26-64F
008/0010
PL-30/NRF-36
E7
Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude models.
NOTICE
The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.
NOTICE