Wireless Temperature and Humidity Sensors

STW-6010, STW-6014, THW-1102

Specifications and design subject to change without notice.

Mounting 

Select a location

Install the sensor on an inside wall where it can 

sense the average room temperature. Avoid locations 

with direct sunlight, heat sources, windows, air 

vents, and air circulation or obstructions such as 

curtains, furniture, etc.

Mount the sensor in an area with a minimum 

illumination of 200 lux for three to four hours 

everyday. The light source can be either artifical 

or daylight. The health and safety at work act 

requires a minimum illumination of 500 lux for 

office workplaces.

The long term illumination should not exceed 

1000 lux.

Avoid recessed areas that are not sufficiently 

illuminated throughout the day.

When using collimated artificial light the angle 

of incidence on the solar cell should be not too 

steep.

The sensors can be mounted with the solar cell 

toward a window but  not in direct sunlight. 

Even occasional direct sunlight can lead to false 

temperature values.

Consider the future use of the room and avoid 

locations that may be used for filing cabinets, 

shelf units, or other large obstructions.

In closed spaces with several walls, the maximum 

range may be less than 33 ft (10 m). In open areas, 

place the sensor no farther away than 98 ft. (30 m) 

from the receiver or gateway. See the publication 

Planning Guide For Wireless Sensor Networks

 for 

details.

Remove the sensor body from the back panel

The sensor body is held to the black, back panel by 

three, small, round pegs that fit in the holes of the 

sensor body. The bottom peg is a spring tab and 

snaps into the center bottom hole.

1.  With a small Phillips screwdriver or hex wrench, 

press in and hold the tab button that snaps into 

the center hole on the bottom cover.

2.  Carefully pull or pry the back panel from the 

sensor body.

Install the optional battery

A single CR1225 lithium coin battery may be 

installed for locations that do not have enough 

sustained light to maintain sensor operation.
3.  Remove the sensor body from the back panel.
4. 

Position the CR1225 battery with the plus (+) 

symbol visible.

5. 

Slide the battery into the battery holder.

6.  Install the sensor.

STW-6010 and THW-1102

STW-6014

Installation Guide

CR1225 lithium 

coin battery

Battery holder