background image

STE-1421/1422 

Installation Guide

© 2005 KMC Controls, Inc.   

717-019-17B

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com

[email protected]

Maintenance

No routine maintenance is required.  Each compo-

nent is designed for dependable, long-term reliability 

and performance.  Careful installation will also 

ensure long-term reliability and performance.

Specifications

Standard Lengths

 

4" (STE–1421), 6" (STE–1422)

Sensor  

 

Type III, 10K ohm @ 77° F (25° C)

Accuracy 

 

 

± 0.36° F (± 0.20° C)

Temperature Limits

  –4° to 221° F (–20° to 105° C)

Wiring 

 

 

22 AWG wire leads

Case 

 

 

Black plastic standard; 

 

 

 

metal optional

BACstage

1.  In the BACstage software main menu, select 

Objects

 > 

Inputs

.

2.  Click 

Edit

.

3.  Type in a name in the 

Description

 field (up to 32 

characters) and/or 

Label

 field (up to 16 characters).

 

Note:  No two labels or descriptions in a controller can 

be identical.

4.  Select 

Object Type: Analog

 if it is not the default.

5.  Select 

Device Type: KMC10K Type III

.

6.  Select 

Units: °F

 or 

°C

.

7.  Click 

End Edit

.

8.  Click 

Yes

 for “Send Update Notification Now?”

9.  In the BACstage software main menu, select 

Device

 > 

Device Tables

 > 

KMC10K Type III Table

.

10. Click 

Edit

.

11. Click 

Defaults

 (values will fill in).

12. Click 

End Edit

.

13. Click 

Yes

 for “Send Update Notification Now?”

14. Click 

OK

.

WinControl

1.  In the WinControl software main menu, select 

Control

 > 

Inputs

.

2.  Click 

Edit

.

3.  Type in a name in the 

Description

 field (up to 20 

characters) and/or 

Label

 field (up to 8 characters).

 

Note:  No two labels or descriptions in a controller can 

be identical.

4.  Click 

Units

 (which opens the Configure Inputs 

screen).

5.  Select 

Type: Analog

 if it is not the default.

6.  Select 

Deg F

 (or 

C

KMC10K Type III

.

7.  Optionally, adjust the 

Calibration

 value.

8.  Optionally, change 

Format

 from 0 to the desired 

number of temperature decimal places.

9.  Optionally, change the 

Average

 to the desired 

number of thermistor readings averaged before 

displaying the result.

10. Click 

OK

.

11. Click 

End Edit

.

12. Click 

OK

.

Controller Configuration

Note: Controller configuration instructions are given for both WinControl and BACstage.  See the relevant software 

section.