STE-1421/1422
2
Installation Guide
© 2005 KMC Controls, Inc.
717-019-17B
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
Maintenance
No routine maintenance is required. Each compo-
nent is designed for dependable, long-term reliability
and performance. Careful installation will also
ensure long-term reliability and performance.
Specifications
Standard Lengths
4" (STE–1421), 6" (STE–1422)
Sensor
Type III, 10K ohm @ 77° F (25° C)
Accuracy
± 0.36° F (± 0.20° C)
Temperature Limits
–4° to 221° F (–20° to 105° C)
Wiring
22 AWG wire leads
Case
Black plastic standard;
metal optional
BACstage
1. In the BACstage software main menu, select
Objects
>
Inputs
.
2. Click
Edit
.
3. Type in a name in the
Description
field (up to 32
characters) and/or
Label
field (up to 16 characters).
Note: No two labels or descriptions in a controller can
be identical.
4. Select
Object Type: Analog
if it is not the default.
5. Select
Device Type: KMC10K Type III
.
6. Select
Units: °F
or
°C
.
7. Click
End Edit
.
8. Click
Yes
for “Send Update Notification Now?”
9. In the BACstage software main menu, select
Device
>
Device Tables
>
KMC10K Type III Table
.
10. Click
Edit
.
11. Click
Defaults
(values will fill in).
12. Click
End Edit
.
13. Click
Yes
for “Send Update Notification Now?”
14. Click
OK
.
WinControl
1. In the WinControl software main menu, select
Control
>
Inputs
.
2. Click
Edit
.
3. Type in a name in the
Description
field (up to 20
characters) and/or
Label
field (up to 8 characters).
Note: No two labels or descriptions in a controller can
be identical.
4. Click
Units
(which opens the Configure Inputs
screen).
5. Select
Type: Analog
if it is not the default.
6. Select
Deg F
(or
C
)
KMC10K Type III
.
7. Optionally, adjust the
Calibration
value.
8. Optionally, change
Format
from 0 to the desired
number of temperature decimal places.
9. Optionally, change the
Average
to the desired
number of thermistor readings averaged before
displaying the result.
10. Click
OK
.
11. Click
End Edit
.
12. Click
OK
.
Controller Configuration
Note: Controller configuration instructions are given for both WinControl and BACstage. See the relevant software
section.