Procedure
Detailed steps
Sensor display
7
Set the damper direction to
close.
1. Press the
or
buttons to which direction to
damper moves to close.
CCW
—The actuator turns counterclockwise to close
the damper.
CW
—The actuator turns clockwise to close the
damper.
2. Press the
Set
Point
button to save the damper option and
advance to the next function.
CCW
DDIR
8
Select a new configuration
function or exit.
1. Press the
or
buttons to select one of the
following:
l
STPT
,
FLOW
,
ADVC
. or
RSTR
options
l
BACK
to choose another configuration function
l
EXIT
to return to the temperature display.
2. Press the
Set
Point
button to select the next function.
BOX
Procedure to set the box functions (continued)
Set the airflow setpoints
The airflow setpoints set the airflow limits for the VAV terminal unit.
l
Airflow heating and cooling minimum and maximum limits
l
Auxiliary flow setpoint (optional)
l
Minimum and maximum fan speeds (optional)
Setting the airflow setpoints requires entering Password 2 which is described in the topic
Getting started with configuration
Note:
If the VAV unit is a heat only or cooling only unit, the airflow setpoints for the unused mode
must be set within the range of the mode in use. Failure to set the unused setpoints
correctly will result in unpredictable or erroneous air balancing settings.
Tip:
Once the following procedure is started, all steps must be completed in order.
SimplyVAV
Section 4: Configuring the controllers
Revision H
29
Содержание SimplyVAV BAC-8001
Страница 1: ...SimplyVAV Application and Installation Guide Revision H ...
Страница 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Страница 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Страница 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Страница 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...