background image

MEP-5062/5072/5372 

Installation Guide

Installation Guide

Direct-Coupled, Proportional, ControlSet

®

 Actuators

MEP-5062/5072/5372 

 

HFO-0011 Shaft Adaptor

Side 

View

Mounting

1.  Ensure that the damper can move freely through 

its entire range of motion. Fix any binding before 

installing the actuator. Turn the damper blade to 

its fully closed position.

2.  Determine the needed direction of rotation and 

relative positions of damper and actuator. See the 

Adjustments section on the next page.

2.  Press and hold the gear disengagement button 

(see the Front View illustration), rotate the 

actuator to the fully closed position, and release 

the lever.

NOTE:  Depending on the damper-seal design, 

backing the actuator off its stop 

approximately 5° may provide tight 

damper shut-off.

3.  Align the actuator and slide it onto the standard 

1/2" diameter (13 mm) damper or valve shaft. 

(For a 3/8" shaft, see the HFO-0011 Shaft Adaptor 

section on the next page.)

4.  Insert the non-rotation bracket (HMO-1003, 

supplied) into the slot at the base of the actuator 

and secure the bracket with two (2) #8 or #10 

self-tapping screws. (See the Front View and Side 

View illustrations.)

5.  Leaving a gap between the actuator and 

mounting surface to prevent any binding, tighten 

the two 5/16-18 setscrews.

Wiring

Fail-Safe Direction

(on MEP-5372 Only) 

Operate with Increasing Voltage 

in Clockwise (CW) Direction

Operate with Increasing Voltage in 

Counterclockwise (CCW) Direction 

Connect wiring according to the diagram. See the 

Accessories/Repair Parts section for connection 

accessories.

Front 

View

Отзывы: