background image

MEP-3001/3006 

Installation and Operation Guide

© 2014 KMC Controls, Inc.   

006-019-01A

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Maintenance

These actuators are noise-free and maintenance-free. 

Careful installation will help ensure long-term reli-

ability and performance.

Operation

After the mechanical and electrical installations have 

been completed, cycle the actuator to verify opera

-

tion. (See Illustrations 4 and 5.)

When power is applied to the actuator, the tem

-

perature of the heating element rises, causing the 

solid expansion medium to expand and stroke the 

attached valve body. The valve starts to open after 

preheating for approximately 1 minute if the heating 

element is switched on in a cold (room temperature) 

state, and achieves the maximum stroke after (ap

-

proximately) another 3-1/2 minutes. At power-off, 

the expansion element cools down, and the spring 

closes the valve.

De-energized position (gap closed):
• 

For MEP-3001s, the actuator shaft 
is extended and the valve is closed.

• 

For MEP-3006s, the actuator shaft 
is retracted and the valve is open.

(Fully) energized position (gap open):
• 

The MEP-3001 has been connected 
to the power supply for at least 
4-1/2 minutes. The actuator shaft is 
retracted and the valve is open.

• 

The MEP-3006 has been connected 
to the power supply for at least 
4-1/2 minutes. The actuator shaft is 
extended and the valve is closed.

Select Specifications

Power

 

24 VAC (± 20%), 50/60 Hz,

 

Class 2 only, 6 VA max. 

Control

 

Two-position or time-propor-

tional

Primary Fuse

 

Must supply externally

Nominal Force

 

22.5 in-lb. (100 N•m)

Stroke Maximum

 

0.18 inches (4.5 mm)

Positioning Time

 

270 sec. @ 68° F (20° C)

Weight

 

0.4 lb. (0.18 kg)

Mounting Location 

NEMA 3 (IP54), interior only

Approvals

 

Conforms to CE requirements

De-energized Position

MEP-3001 (NC) 

Actuator shaft extended, valve 

closed (for VEP-12/22/34 se-

ries)

MEP-3006 (NO) 

Actuator shaft retracted, valve 

open (for VEP-11/21/37 series)

Temperature Limits

Medium 

34 to 230° F (1 to 110° C)

Ambient  

41 to 122° F (5 to 50° C) @ 0 to 

85% RH (non-condensing)

Shipping 

–4 to 140° F (–20 to 60° C) @ 0 

to 95% RH (non-condensing)

UP

Illustration 4—Position Indication

Illustration 5—Opening and Closing Times

More Information

For more information 

on applications, see the

 

REE-5017

 on the 

KMC 

web site

.

See also, the

 

REE-5106

.

Отзывы: