KMD–5210 Installation and Operation

Revision E

Configuration and programming

Configuring a controller with HCM

33

KMC digital network configuration

The entries in the table 

HCM Configuration Screen setup fields

 on page 33

 are 

required for controller-to-controller communications on a KMC controls 
digital network.

Table  4-1  HCM Configuration Screen setup fields

Setting

Description

Address

Enter the address that is assigned to the controller on the network. 
Valid numbers are 1–31. This address is also the BACnet MS/TP 
MAC address in KMD-5210–002 controllers.

Last Panel

Check this box only if the controller is assigned to the highest 
address number in the system. This controls token passing in the 
network. Last Panel is not applicable for Tier 1 controllers 
connected with Ethernet.

SubLAN A
SubLAN B
Main Network
BACnet

Sets the connection speed of the Tier1, Tier 2 or BACnet MS/TP port 
to which the LAN controller is connected. Set each baud to match 
the baud of the other controllers on each network.

Modem String For Firmware 4.0 and later: The string 

AT&A &B1 &C1 &D2 &H1 

&K0 &R1

 is stored in Flash memory and cannot be changed. Entries 

in 

Modem String

 are sent to the modem after the default string is 

sent. This provides a method to override settings in the default 
string. For example, entering ATS0=5 sets the modem to answer on 
the fifth ring.

Firmware earlier than 4.0: The controller automatically transmits the 
default initialization string 

AT&A &B1 &C1 &D2 &H1 &K0 &R1 

to 

the modem. The default string can be modified by making changes 
in 

Modem String

.

See 

Installing a modem interface

 on page 23

 for modem installation 

and switch settings.

Computer A

Use this field to set the communication speed if a PC is directly 
connected to this port.

Computer B

Use this field to set the communication speed if a PC is directly 
connected to this port. If you are using the modem port on the LAN 
controller, check the 

Modem

 box to indicate a modem is attached 

to the controller. If you have a modem attached, you cannot use the 
Computer B connector.

I/O Card 
Configuration

Use the fields in this area to enable communications with input or 
output cards connected to the controller. Click on the button to step 
through the choices. Input cards are connected to the controller 
starting at position #1; output cards are connected starting at 
position #8. If a port is unused, leave it marked as 

Unused

 in HCM.

Содержание KMD-5210

Страница 1: ...Revision E Installation and Operation Guide KMD 5210 LAN Controller KMD 5210 001 LAN Controller with BACnet 802 3 KMD 5210 002 LAN Controller with BACnet MS TP 883 019 07E ...

Страница 2: ...out the written permission of KMC Controls Inc Printed in U S A Disclaimer The material in this manual is for information purposes only The contents and the product it describes are subject to change without notice KMC Controls Inc makes no representations or warranties with respect to this manual In no event shall KMC Controls Inc be liable for any damages direct or incidental arising out of or r...

Страница 3: ... BACnet networks 18 Planning for input and output modules 20 Module installation 21 Connecting Power 22 Connecting to a Computer 23 Section 3 Operation Applying power 27 Lights and indicators 27 Resetting the controller 29 Section 4 Configuration and programming Related materials 31 Programming Considerations 31 Configuring a controller with HCM 32 Programming for BACnet in WinControl XL 36 Access...

Страница 4: ...KMC Controls Revision E 4 ...

Страница 5: ... Tier 2 networks with two dedicated EIA 485 ports Up to 32 KMD 5210 controllers can be integrated into a single peer to peer network each supporting up to 124 nodes on a Tier 2 network The controller also supports remote access through a modem port and provides two ports for direct connection with up to two PCs The firmware in the controller uses a high level easy to learn programming language to ...

Страница 6: ...t digital to analog D A Communications Tier 1 EIA 485 protocol at rates up to 38 kilobaud Connector type is a three screw terminal block 12 22 AWG wire Note Use the Tier 1 connection only when replacing KMD 5110 MultiNet controllers and Ethernet is not available Contact KMC Controls techncial support for networking details Tier 2 A and B EIA 485 protocol at rates up to 38 kilobaud Connectors are t...

Страница 7: ... 5 user defined Logging Trend Logs 96 trend logs each supporting up to 6 analog digital or virtual elements or points Runtime Logs 28 runtime logs with time date stamp and cumulative runtime Schedules Weekly Schedule 32 schedules with 2 override days Annual Schedule 16 for holiday schedules Alarms Alarm buffering for up to 128 alarms 50 alarm messages for distribution On board 68 character alarm o...

Страница 8: ... Humidity 0 95 RH non condensing Weight 1 8 pounds 816 grams Compatibility Software WinControl XL Plus 1 06 or later TotalControl 1 8 1 or later Controllers Compatible with Tier 1 controllers firmware build 2 01 or later Dimensions Illustration 1 1 KMD 5210 Components Table 1 1 KMD 5210 Dimensions A B C D E F Height not shown 10 50 in 6 50 in 0 25 in 10 00 4 00 in 1 25 in 0 98 in 267 mm 165 mm 6 m...

Страница 9: ...ble KMD 5661 14 inch 36 cm ribbon cable KMD 5662 19 inch 48 cm ribbon cable KMD 5663 24 inch 61 cm ribbon cable Power KMD 5563 International ready power supply 120 240 volts AC 1 35 amperes XEE 6112 100 100 VA Transformer 24 volts AC required only for KMD 5221 output module Upgrades HTO 1102 Flash Kit Module KMD BAC 5XXX BAC 7XXX Replaces KMD 5696 Enclosures HCO 1035 Panel Enclosure 20 x 24 x 6 in...

Страница 10: ...Before installing the KMD 5210 LAN Controller take some time to become familiar with the controller layout and components Illustration 1 2 Controls and indicators Reset button Beneath cover Power Tier 1 EIA 485 Tier 2 EIA 485 Modem BACnet MS TP EIA 232 for PC Ethernet and BACnet 802 3 LED Status Display ...

Страница 11: ...ment itself To promote safety we use hazard alert labeling in this manual Follow the associated guidelines to avoid hazards Danger Danger represents the most severe hazard alert Bodily harm or death will occur if danger guidelines are no t followed Warning Warning represents hazards which could result in severe injury or death Caution Caution indicates potential personal injury or equipment or pro...

Страница 12: ...KMC Controls Revision E About the LAN controller Safety Considerations 12 ...

Страница 13: ...s on each side of the controller to securely fasten it to a flat surface See Illustration 1 2 on page 10 for mounting hole locations and dimensions To maintain RF emission specifications use either shielded connecting cables or enclose all cables in conduit Note Provide sufficient clearance around the controller for cables and wiring Allow a minimum of 3 inches 7 6 cm of clearance at the top edge ...

Страница 14: ... 5 6 7 8 STATUS H O A STATUS H O A O R O R O R STATUS H O A O R STATUS H O A O R STATUS H O A O R STATUS H O A O R STATUS H O A O R STATUS H O A 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 STATUS KMD 5210 CONNECTOR INPUT JUMPERS 4 20 MA 1K PULL UP 10K PULL UP NO PULL UP TRANSDUCER POWER OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 15 VDC INPUT INPUTS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 STATUS...

Страница 15: ...the controller to the network by connecting a standard 10BaseT Ethernet cable CAT 5 to the Ethernet BACnet port on the controller and to a port on the network hub or router See Ethernet Settings later in this guide for recommended Ethernet Software Settings Note For reliable operation use CAT 5 or equivalent Ethernet cables for all connections If cables are custom made they must meet the CAT 5 spe...

Страница 16: ...lent 18 gauge twisted shielded 50 picofarads or less for all EIA 485 network wiring Wiring notes All EIA 485 network segments KMC protocol or BACnet use the same wiring principles Use approved shielded cable and the following principles when connecting a controller to a Tier 2 sub LAN network Connect no more than 31 KMC addressable controllers or devices to the Tier 1 RS 485 connector Connect no m...

Страница 17: ... system wiring Termination jumpers are located on both sides of each EIA 485 connector one each for the A and B terminals see Illustration 2 5 To activate the end of line termination leave the jumpers in place If termination is not required position the jumpers so they only cover one pin on the header Illustration 2 4 Typical EIA 484 Wiring Configuration Illustration 2 5 End of line Termination Ju...

Страница 18: ...atures Note The BACnet options are licensed for each controller To upgrade a KMD 5210 controller to BACnet contact KMC Controls for license information BACnet 802 3 The KMD 5210 001 the BACnet 802 3 version of the LAN controller connects to the LAN in the same manner as the standard LAN controller See Network connections on page 14 The BACnet internetwork most likely will use one or more BACnet ro...

Страница 19: ...MS TP Connect a KMD 5210 002 controller to a BACnet MS TP network at the connector EIA 485 See EIA 485 networks on page 16 for network wiring techniques To configure a KMD 5210 002 for network connections see BACnet configuration on page 35 Illustration 2 7 BACnet MS TP connections Shield ...

Страница 20: ...ination of up to eight modules Each module connects to the controller using a flat ribbon cable When connecting input and output modules use the following guidelines Connect the first KMD 5220 input module to connector I O Card 1 add continue adding input modules from left to right Connect the first KMD 5221 output module to connector I O Card 8 and continue adding output modules from right to lef...

Страница 21: ... orientation of the cable header If the pin 1 edge is reversed the controller will not communicate with the module 3 Connect the other end of the ribbon cable to the input or output module You may find it necessary to fold the cable to properly route it to the module To accommodate turns fold the cable gently to change direction To make a fold overlay the cable at a right angle and press gently un...

Страница 22: ...ule for details Connecting Power Each KMD 5210 LAN Controller requires a KMD 5563 power supply for operating power Mount the power supply in a convenient location near the KMD 5210 and route the supply cable to the controller The controller will automatically power on when the power connection is complete The controller does not use an power switch See Applying power on page 27 for additional info...

Страница 23: ...ol Basic functions TPAGE and NPAGE If the modem port is enabled Computer B port is disabled and is not available for direct connection with a computer Note KMC Controls recommends using U S Robotics modems for off site communications KMC does not offer support for other modem installations To install a modem 1 Connect a a standard DB 9 to DB 25 computer to modem cable between the KMD 5569 modem an...

Страница 24: ...hernet Refer to the section Configuring a controller with HCM on page 32 for additional information Direct Serial Port Connection Two RS 232 ports are provided on the controller for connecting a PC directly to the controller Connect the PC to the controller using a KMD 5672 PC to Controller cable Refer to Illustration 2 12 Table 2 1 Configuration switches Firmware 4 0 and later 1 2 3 4 5 6 7 8 Up ...

Страница 25: ...nd Operation Revision E Installation Connecting to a Computer 25 Note EIA 232 port B is assigned the same address as the modem port When the modem port is in use a PC cannot be connected to the controller through serial port B ...

Страница 26: ...KMC Controls Revision E Installation Connecting to a Computer 26 ...

Страница 27: ...following section Lights and indicators The controller provides a number of different status and diagnostic indicators These are described in this section Isolation bulbs Located near each EIA 485 connector you will find two small glass bulbs These serve as protective isolation devices for the Tier 2 and BACnet MS TP EIA 485 networks The bulbs serve three functions When illuminated they indicate i...

Страница 28: ...x This green LED blinks when the controller is transmitting data to the Ethernet network Ethernet Rx This green LED blinks when the controller is receiving data from the Ethernet network Ethernet Collision This red LED blinks when there is a collision of data packets on the Ethernet While collisions are normal excessive collisions indicate a problem somewhere in the network Power The green power L...

Страница 29: ...bbon cables 4 Depress and hold the Reset Button while reestablishing power to the LAN Controller 5 Continue to hold the reset button until MAIN Tier 2 A and Tier 2 B LEDs light Caution Do not remove power during the reset process Damage may result to the board if this happens 6 Release the Reset Button and allow the controller to continue to power up steady blink Power LED 7 Remove power from cont...

Страница 30: ...KMC Controls Revision E Operation Resetting the controller 30 ...

Страница 31: ...e the following reference materials WinControl XL Plus User s Manual and installed help HCM reference guide TotalControl Design Studio Reference Guide System plans with controller addresses Programming Considerations The design of the KMD 5210 LAN Controller provides areas where specific user programs may be stored This allows a great deal of versatility and function in the way the controller is u...

Страница 32: ...prevent disruption to other controllers on the network disconnect the network cables or remove the isolation bulbs on the controller prior to starting HCM 1 Start HCM connect the controller to the computer and establish communications with the controller 2 Make the entries as described in the section KMC digital network configuration on page 33 3 Setup the Ethernet routing table See Ethernet routi...

Страница 33: ... in Flash memory and cannot be changed Entries in Modem String are sent to the modem after the default string is sent This provides a method to override settings in the default string For example entering ATS0 5 sets the modem to answer on the fifth ring Firmware earlier than 4 0 The controller automatically transmits the default initialization string AT A B1 C1 D2 H1 K0 R1 to the modem The defaul...

Страница 34: ...and Ping the controller s IP address If the controller is operating correctly you should receive a response to the ping command If you are unfamiliar with the above steps contact KMC Controls for assistance Table 4 2 Tier 1 LAN controller Ethernet settings Setting Description IP address Supplied by network administrator Enter the address next to the panel address of the LAN Controller MTU 1400 or ...

Страница 35: ...net system designer Instance numbers are required must be unique among all devices on the internetwork and range from 0 to 4 194 303 Name A required 16 character label of the device Name must be unique among all devices on the internetwork The set of characters used in Name is restricted to printable characters Location Optional information used to further identify a piece of equipment Description...

Страница 36: ...the KMD point with both a description and a label in WinControlXL Plus In TotalControl configure the point with both a description and name Use BAC SET BAC GET and BAC RLQ in Control Basic to read and write other objects on other BACnet devices KMC Controls recommends that all BACnet services have adequate error handling protocols within your control program A sample Control Basic code segment is ...

Страница 37: ...the network If the LAN Controller must communicate with a network where a firewall is in place the following actions must be taken LAN controllers communicate through one of three Ethernet Ports WinControl to LAN Controller UDP 21068 LAN Controller to LAN Controller UDP 21069 LAN Controller to LAN Controller UDP 21070 These ports must be open for communications to pass through a firewall If the LA...

Страница 38: ...KMC Controls Revision E Configuration and programming System time keeping 38 ...

Отзывы: