background image

Mounting Continued

Setpoint Stops

Setpoints can be locked, or limited, using setpoint stops.  Each HFO–0027
Setpoint Stop Strip (accessory sold separately) contains four stops.

1. Break a stop from the strip by gently folding on the seam with pliers.

2. Insert a stop into the slider track  on one or both sides of the slider.

3. Repeat for second slider.

Scale Plates (required)

1. Install scale plate under the setpoint indicators.
2. Align mounting holes.
3. Insert the two retaining pins (HPO–0046, supplied) into the holes.
4. Twist pins 1/4 turn to firmly seat.

Covers

A symbol-coded label strip is included with the window style covers for
setpoint indication.

1. Remove the window by applying light pressure on its underside and

flexing upward.

2. Peel-off correct identity label from the strip of labels provided.
3. Position the label on the covers’ recessed area.
4. Snap window back in place.
5. Slide cover onto base.
6. Locate the set screw on each of the thermostats short sides.
7. Using a 1/16" hex/key wrench, turn set screws outward CCW until the

cover is secure. Turn set screws CW to remove cover.

Wiring

Removeable thumb adjusters. See NOTE

NOTE:

 When using a blank cover, remove the finger pads on the setpoint sliders. Hold the slider in

place, insert a small flatblade screwdriver into the slot in the metal slider. Twist the screwdriver
slightly to pop the pad off.

Setpoint Stops

Refer to the project plans, as built drawings or table

on the oposite pages for more information.

Содержание CTE–5101

Страница 1: ...e through the backplate and decorative trim plate opening included with HMO 5024 5026 or 5030 5031 Be careful not to damage the trim plate while wiring 5 Connect the thermostat s wires according to it s particular application Refer to project drawing or the wiring chart 6 Position the trim plate between the backplate and the thermostat cover removed 7 Align the mounting holes and secure the assemb...

Страница 2: ...ve the window by applying light pressure on its underside and flexing upward 2 Peel off correct identity label from the strip of labels provided 3 Position the label on the covers recessed area 4 Snap window back in place 5 Slide cover onto base 6 Locate the set screw on each of the thermostats short sides 7 Using a 1 16 hex key wrench turn set screws outward CCW until the cover is secure Turn set...

Страница 3: ... request minimum flow using the minimum dial DA Cooling Set point Room Temp RA heating Set point Room Temp 8 Adjust set point to request maximum flow using the max dial RA Heating Set point Room Temp DA Cooling Set point Room Temp Note Limits may be set at the CSP or the thermostat If setting min max limits at the thermostat CSP s Min dial must be turned fully CCW to 0 AND the Max dial must be tur...

Страница 4: ...6553 U S A TEL 574 831 5250 FAX 574 831 5252 E mail info kmccontrols com Maintenance No routine maintenance is required Each component is designed for dependable long term reliability and performance Careful installation will also ensure long term reliability and performance ...

Отзывы: