CTE-5001/5011 

Installation Guide

Adjustments and Calibration

Thermal calibration is not required. Minimum and 

maximum control points can be calibrated before or 

after the thermostat has been installed.
NOTE:  In 2009, the boards were changed, and the 

new potentiometers can only be adjusted 

from the front of the board (instead of from 

both the front and the back as in the older 

boards).

To set the flow rates and the deadband:
1.  Remove the cover by pulling up on it from the 

bottom.

2.  With a voltmeter, measure the voltage between 

Common (B) and Out (D).

3.  Adjust the 

Minimum

 Flow—turning the 

potentiometer 

clockwise

 (CW) 

increases

 the flow:

•  For 

DA

, turn the setpoint dial to the 

highest

 

(warmest) temperature, and (with a small 

Phillips screwdriver) adjust the Minimum 

Flow.

•  For 

RA

, turn the setpoint dial to the 

lowest

 

(coldest) temperature, and (with a small 

Phillips screwdriver) adjust the Minimum 

Flow.

4.  Adjust the 

Maximum

 Flow—turning the 

potentiometer 

clockwise

 (CW) 

increases

 the flow:

•  For 

DA

, turn the setpoint dial to the 

lowest

 

(coolest) temperature, and adjust the 

Maximum Flow. Always adjust Maximum 

Flow to a value higher than the Minimum 

Flow—if in doubt, turn Maximum Flow 

fully CW (increase) at the beginning of the 

adjustment.

•  For 

RA

, turn the setpoint dial to the 

highest

 

(warmest) temperature, and adjust the 

Maximum Flow. Always adjust Maximum 

Flow to a value higher than the Minimum 

Flow—if in doubt, turn Maximum Flow 

fully CW (increase) at the beginning of the 

adjustment.

5.  Reinstall the cover.
NOTE:  If using a

 changeover

 application, be aware 

of which mode the system is in and follow 

the appropriate procedure for adjusting DA 

or RA minimum and maximum flows. To 

help determine the mode, turn the Min. pot 

CCW to zero and Max. pot CW to full and 

determine if the output increases or decreas-

es as the setpoint is moved back and forth.

© 2011 KMC Controls, Inc.   

831-019-01G

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Important Notices

The material in this document is for information 

purposes only. 

The contents and the product it 

describes are subject to change without notice.

 

KMC Controls, Inc. makes no representations or 

warranties with respect to this document. In no event 

shall KMC Controls, Inc. be liable for any damages, 

direct or incidental, arising out of or related to the 

use of this document.

Maintenance

Careful installation will also ensure long-term reli-

ability and performance. Remove dust accumulation 

as necessary from slots in top and bottom. Clean 

cover with a soft, damp cloth and mild soap.

Accessories

HMO-5001 

Dual toggle bolt for backplate 

mounting to drywall

HMO-5014 

Insulating stand-off, light almond

HMO-5016 

Insulating stand-off, white

HMO-5036 

Adapter backplate to vertical 

handy box, light almond

HMO-5037 

Adapter backplate, vertical, 

white

HMO-5038 

Adapter backplate to horizontal 

handy box, white

HMO-5039 

Adapter backplate, horizontal, 

light almond

HPO-0031 

Setpoint cover, white

HPO-0032 

Setpoint cover, light almond

REE-1014 

Relay module, heat/cool change-

over for CTE-5000 series

SSE-2001/2002 

Duct flow/temperature sensors 

for VAV systems

XEE-4002 

Power supply, 24 VAC to 9.1 VDC

NOTE:  For more accessories, see the Thermostats 

section of the Electronic and Pneumatic 

Condensed Catalog.

Отзывы: