PWR
KMB systems
7. Technical parameters
type: PWR 1N 60W 24V
type: PWR 1A 60W 24V
input
Terminals
0,2÷4mm
2
(24÷12AWG), 32A, 0,5÷0,6Nm
Nominal supply voltage
~
120÷400V, 50÷60Hz
Supply voltage range
~
90÷460V, 47÷63Hz, =127÷340V
(see charts)
efficiency
(typical)
85% @
~
230V, 60W
83% @
~
230V, 60W
power, PF
(typical)
140VA, 0,51 @
~
230V, 60W
125VA, 0,58 @
~
230V, 60W
Consumption with no load
(typical)
<30mA, 7VA, 2W @
~
230V
(without accu)
Inrush current
(typical)
60A @
~
230V
60A @
~
230V
Mains failure immunity
(typical)
80ms @
~
230V
Based on accu and load
over-voltage category, safety
300V CAT IV do 2000m.n.m. / 300V CAT III do 5000m.n.m.
ČSN EN 61010-1, ČSN EN 60950-1, protection class I,
c,
isolating voltage & resistance
(in / out)
3kV
~
/1min, reinforced insulation, >100MΩ/500V=
output and accumulator
terminals
0,2÷2,5mm
2
(24÷14AWG), 24A, 0,5÷0,6Nm
insulation, safety
SELV
, galvanically insulated from supply voltage
Nominal output voltage
24V
24V
Nominal output power
60W
60W
Nominal output current / range
2,5A / 0÷3,75A
1,4A / 0÷2,2A
charging current 0,75A
total current 3,0A
accuracy of output voltage / range
±1%
21÷27,6V
ripple and noise(max.)
240mV
P-P
---
over-voltage protection
27,6V
29V
accu. protection (disconnection)
---
21±1V
overload protection (max.)
150%
150%
alarm, signal output
terminals
0,2÷1,5mm
2
(24÷16AWG), 12A, 0,2÷0,25Nm
Insulation, safety
SELV
, galvanically insulated from supply voltage
SSR output
S
30mA/24V=, against
⊝
pole
general
protection, pollution degree
IP20, 2, (for 3 contact manufacturer)
operating temperature
-30÷70°C
(see chart)
-20÷70°C
(see chart)
storage temperature
-40°C÷85°C
Operating and storage humidity
0÷95% RH, non-condensing
EMC – emission
ČSN EN 55011
,
ČSN EN 61000-3-2/-3 – class B
EMC – immunity (61000-4-2/3/4/5/6/8/11)
ČSN EN 61326-1, ČSN EN 61000-6-2, ČSN EN 61000-6-5
dimension
W 58,6mm x H 109,4mm x D 104,9mm, see drawing
weight, nett
0,25kg (without accu.)
6